Setting The Wireless Remote Controller - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
1.2

Setting the Wireless Remote Controller

Introduction
To set the wireless remote controller, you have to set the address for:
Setting the
The address for the receiver of the wireless remote controller is factory set to 1. To change this
address for the
setting, proceed as follows:
receiver
Test Operation
The receiver of the wireless remote controller
The wireless remote controller.
Step
Action
1
Turn OFF the power.
2
Remove the sealing pad on the top of the receiver.
3
Set the wireless address switch (SS2) according to the table below. You can find the
wireless address switch attached on the PCB of the receiver and it is visible through the
small opening on the back of the receiver.
Unit No.
SS2
4
If you use a wired and a wireless remote controller for one indoor unit, proceed as
follows:
1. Set the wired remote controller to MAIN: On the remote controller.
2. Set the wireless remote controller to SUB: On the receiver with the MAIN/SUB switch
(SS1).
MAIN/SUB
SS1
5
Seal off the opening of the address switch and the MAIN/SUB switch with the attached
sealing pad.
6
Make sure to also change the address on the remote controller.
Sealing pad
Small opening
Receiver
No. 1
No. 2
MAIN
S
M
Sealing pad
Small opening
Receiver
Test Operation
S
M
3
2
1
No. 3
SUB
S
M
S
M
3
2
1
85