RZQ100~140C7, RZQS125·140C7V1B
2.7

Removal of Four Way Valve

Procedure
Step
Recover the refrigerant.
According to the
procedure for the removal
related to the outside
panel, remove the front
panel (2) and the side
panel.
According to the
procedure for the removal
of switch box, remove the
switch box.
Unscrew the one screw
1
that fixes the coil for the
four way valve, and
then remove this coil.
Remove brazing from
2
the four places, and
then remove the four
way valve.
(Refer to point column.)
284
Warning
Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Procedure
Be sure to remove the four
way valve only after the
refrigerant is completely
recovered.
Brazing
Four way valve
Coil for four
way valve
To prevent the four way
Brazing
valve from exceeding a
Screw
temperature of 120°C,
conduct brazing work while
cooling the valve with wet
cloths or else.
SiBE28-804
Points
Removal Procedure