Outdoor Malfunctions - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
5.2

Outdoor Malfunctions

Outdoor Unit
Remote
Malfunction
Controller
Display
E1
E3
E4
E5
E7
E9
F3
H3
H9
J1
J3
J5
J6
J7
J8
L1
L4
L5
L8
L9
LC
P1
P4
PJ
U0
U2
Notes:
1. Possibility of open phase in power supply.
Troubleshooting
Location of Malfunction
Other
PC Board
than PC
Outdoor
Indoor
Board
Unit
Unit
Troubleshooting by Remote Controller Display / LED Display
Contents of Malfunction
Remote
Controller
Outdoor unit PC board
malfunction
Abnormality of high pressure
(HPS)
Abnormality of low pressure
(outdoor)
Compressor motor lock
malfunction
Malfunction of outdoor unit fan
motor
Malfunction of Electronic
expansion valve
Discharge pipe temperature
malfunction
Faulty high pressure switch
(HPS)
Malfunction of outdoor air
temperature sensor system
Malfunction of pressure sensor
Malfunction of discharge pipe
temperature sensor system
Suction pipe thermistor
malfunction
Malfunction of heat exchanger
temperature sensor system
Malfunction of subcooling heat
exchanger thermistor (outdoor
unit)
Malfunction of liquid pipe
thermistor (outdoor unit)
Outdoor PC board malfunction
High temperature of radiation fin
Overcurrent of DC output
(instantaneous)
Electronic thermal switch
(time lag)
Stall prevention (time lag)
Malfunction of transmission
system (between control PC
board and inverter PC board)
Open phase or voltage
unbalance
Malfunction of radiator fin
temperature thermistor
Error in capacity setting
Gas shortage
Abnormal power supply voltage
Details of
Malfunction
(Reference
Page)
178
179
181
183
185
188
191
193
194
195
194
194
194
194
194
197
199
201
203
205
207
209
210
211
212
214
155

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents