Daikin SkyAir Service Manual page 201

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

Troubleshooting by Remote Controller Display / LED Display
190
A
Actually, it is in wet operation.
Refer to
Check 13,14,15
eliminate the causes of wet operation.
Restart operation.
Does
the malfunction
code "E9"
recur?
NO
∗1: Electronic expansion valve and connector No.
RZQ71~140C7, RZQS71~140C7 → X21A
∗2: Electronic expansion valve connector and
coil resistance criteria
(White)
1
(Yellow)
2
Measurement
spot
3
(Orange)
1 - 6
(Blue)
4
3 - 6
2 - 5
(Brown)
5
4 - 5
(Red)
6
COM (+) (Gray)
RZQ71C7V1B
RZQS71·100C7V1B
∗3: For thermistor temperature and
resistance characteristics, Refer
to
Check 4,5
on
P228~229.
∗4: For voltage characteristics of the
pressure sensor, see the right
figure.
P = 1.38V – 0.69
P : Detected pressure (MPa)
V : Output voltage
(P236~239) to
YES
(Orange)
1
(Red)
2
Criteria
3
(Yellow)
40 ~ 50Ω
40 ~ 50Ω
(Black)
4
40 ~ 50Ω
(Gray)
5
40 ~ 50Ω
(White)
6
RZQ100~140C7V1B
RZQS125·140C7V1B
3.5
3.0
2.5
2.0
1.5
PH
(MPa)
1.0
0.5
0
–0.5
–0.5
0
0.5
1
Output voltage V (V
SiBE28-804
Replace the outdoor PC
board (A1P).
It is believed that factors
(noise, etc.,) other than failure
caused the malfunction.
Measurement
Criteria
spot
1 - 5
40 ~ 50Ω
2 - 5
40 ~ 50Ω
3 - 5
40 ~ 50Ω
4 - 5
40 ~ 50Ω
PH
1.5
2
2.5
3
3.5
)
DC
Troubleshooting