Remote Controller Display Malfunction Code And Contents - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

Procedure of Self-Diagnosis by Remote Controller
3.4
Remote Controller Display Malfunction Code and
Contents
Malfunction Code
A1
Failure of PC board ass'y for indoor unit
A3
Malfunction of drain water level system
A6
Indoor unit fan motor overload / overcurrent / lock (Note 1)
A7
Swing flap motor lock
A8
Abnormal power supply voltage
AF
Abnormal drain water level
AJ
Failure of capacity setting
C1
Failure of transmission (between indoor unit PC
board and fan PC board)
C4
Malfunction of heat exchanger temperature
sensor system
C6
Failure of combination (between indoor unit PC
board and fan PC board)
C9
Malfunction of suction air temperature sensor
system
CJ
Malfunction of remote control air temperature
sensor system
CC
Malfunction of humidity sensor system
E1
Outdoor unit PC board malfunction
E3
High pressure malfunction (outdoor unit)
E4
Abnormality of low pressure (outdoor)
E5
Compressor motor lock malfunction
E7
Outdoor fan motor lock or outdoor fan
instantaneous overcurrent malfunction
E9
Malfunction of electronic expansion valve
(outdoor unit)
F3
Discharge pipe temperature malfunction (outdoor
unit)
H3
Failure of high pressure switch (outdoor unit)
H9
Malfunction of outdoor air temperature sensor
system (outdoor unit)
J1
Malfunction of pressure sensor
J3
Malfunction of discharge pipe temperature
sensor system (outdoor unit)
J3
Malfunction of discharge pipe temperature
sensor system (outdoor unit)
J5
Suction pipe thermistor malfunction
J6
Malfunction of heat exchanger temperature
sensor system (outdoor unit)
J7
Malfunction of subcooling heat exchanger
thermistor (outdoor unit)
J8
Malfunction of liquid pipe thermistor (outdoor unit) Applicable Models : (Note 3)
JC
Malfunction of suction pressure sensor
L1
Outdoor PC board malfunction
L4
Radiation fin temperature rise
L5
Instantaneous over current
L8
Electronic thermal
L9
Stall prevention
LC
Malfunction of transmission system (between
control PC board and inverter PC board)
150
Contents/Processing
Remarks
Activation of float switch during compressor off.
Either capacity data is set incorrectly, or capacity
has not been set for the data IC
Failure of remote controller air thermistor.
Unit can be operated by indoor unit thermistor.
Failure of low pressure sensor system.
Check if the stop valve open.
Compressor motor lock, incorrect wiring.
(Note 2)
Applicable Models : (Note 3)
Applicable Models : (Note 3)
Failure of suction pipe thermister system
(Note 2)
Applicable Models : (Note 3)
Failure of suction pressure sensor system
Applicable Models : (Note 3)
Malfunction of inverter cooling
Possibility of compressor motor grounding or
shortage of motor winding
Possibility of compressor overload, open circuit in
compressor motor
Possibility of compressor seizing
SiBE28-804