2.2

Equipment does not Operate

Applicable Model
All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Supposed
Causes
Troubleshooting
Fuse blown or disorder of contact in operation circuit
Faulty operation switch or contact point
Faulty high pressure switch
Faulty magnetic switch for fan motor
Activation or fault of overcurrent relay for fan motor
Faulty overcurrent relay for compressor
Faulty compressor protection thermostat
Insufficient insulation in electric system
Faulty contact point of magnetic switch for compressor
Malfunction of compressor
Fefective remote controller or low batteries (wireless)
Check if address is set correctly on wireless R.C.
Troubleshooting Based on Equipment Condition