SiBE28-804
2.3
Condensation Avoidance Control
In cooling and dry operation, the following control is carried out in order to prevent dew
condensation when the horizontal blade blows air downward.
[Start condition]
&
[Dew condensation prevention control]
Dry operation with horizontal air flow is carried out for one hour (*1).
Note
1. When there is any change to heating/fan modes, airflow direction and operation ON/OFF
2. *1: For FAQ71, the air flow is 44 degrees downward from the horizontal direction.
Functional Description
FHQ71~125, FAQ71·100
• Horizontal blade is set to downward flow
• Cooling operation (compressor operation) continues for A minutes.
FHQ
A
30 min.
state during dew condensation prevention control, this control is reset.
FAQ
20 min.
Indoor Unit Functional Concept
55