SiBE28-804
5.11 "AF" Malfunctioning Drain System
AF
Remote
Controller
Display
LED indications
The table below shows the LED indications.
Operation
Normal
Malfunctioning
Error generation
The error is generated when the float switch changes from ON to OFF while the compressor is
OFF.
Supposed
The possible causes are:
Causes
Troubleshooting
Error in the drain pipe installation
Malfunctioning float switch
Malfunctioning indoor unit PC board.
Troubleshooting by Remote Controller Display / LED Display
HAP (green)
5
5
HBP (green)
5
5
167