SiBE28-804
Check No.5
Resistance Conversion Table (Discharge Pipe Sensor)
Temperature –
The table below is the discharge pipe thermistor temperature – resistance conversion table.
resistance
Troubleshooting
Temp.
Resist.
(°C)
(kΩ)
-6.0
1120.0
-4.0
1002.5
-2.0
898.6
0.0
806.5
2.0
724.8
4.0
652.2
6.0
587.6
8.0
530.1
10.0
478.8
12.0
432.9
14.0
392.0
16.0
355.3
18.0
322.4
20.0
292.9
22.0
266.3
24.0
242.5
26.0
221.0
28.0
201.6
30.0
184.1
32.0
168.3
34.0
154.0
36.0
141.0
38.0
129.3
40.0
118.7
42.0
109.0
44.0
100.2
46.0
92.2
48.0
84.9
50.0
78.3
52.0
72.2
54.0
66.7
56.0
61.6
48.0
57.0
Troubleshooting by Remote Controller Display / LED Display
Temp.
Resist.
(°C)
(kΩ)
60.0
52.8
62.0
48.9
64.0
45.3
66.0
42.0
68.0
39.0
70.0
36.3
72.0
33.7
74.0
31.4
76.0
29.2
78.0
27.2
80.0
25.4
82.0
23.7
84.0
22.1
86.0
20.7
88.0
19.3
90.0
18.1
92.0
16.9
94.0
15.8
96.0
14.8
98.0
13.9
100.0
13.1
102.0
12.3
104.0
11.5
106.0
10.8
108.0
10.2
110.0
9.6
112.0
9.0
114.0
8.5
116.0
8.0
118.0
7.6
120.0
7.1
122.0
6.7
124.0
6.4
126.0
6.0
128.0
5.7
Temp.
Resist.
(°C)
(kΩ)
130.0
5.4
132.0
5.4
134.0
4.8
136.0
4.6
138.0
4.3
140.0
4.1
142.0
3.9
144.0
3.7
146.0
3.5
148.0
3.3
150.0
3.2
152.0
3.0
154.0
2.9
156.0
2.7
158.0
2.6
160.0
2.5
162.0
2.3
164.0
2.5
166.0
2.1
168.0
2.0
170.0
1.9
172.0
1.9
174.0
1.8
176.0
1.7
178.0
1.6
180.0
1.5