Overview Of The Indoor Safety Devices - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

Troubleshooting by Remote Controller Display / LED Display
5.5

Overview of the Indoor Safety Devices

FFQ35~60
FCQ35~71
FCQ100~140
FBQ35~125
FDQ125
FHQ35~125
FUQ71~125
FAQ71/100
FVQ71~125
158
Thermal protector
Abnormal
>130°C +/-5°C
>130°C +/-5°C
>140°C +/-5°C
N.A.
N.A.
>130°C +/-5°C
>130°C +/-5°C
>130°C +/-5°C
>130°C +/-5°C
Reset (automatic)
<83°C +/-20°C
<83°C +/-20°C
<45°C +/-15°C
N.A.
N.A.
<83°C +/-20°C
<83°C +/-20°C
<83°C +/-20°C
<115°C
Thermal fuse fan motor
N.A.
N.A.
N.A.
>152°C
>160°C
N.A.
N.A.
N.A.
N.A.