Daikin SkyAir Service Manual page 22

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
Specification
Liquid quantity
Liquid type
Liquid diameter (OD)
Gas quantity
Gas type
Gas diameter (OD)
Drain quantity
Drain type
Piping
Drain diameter (OD)
connections
Piping length min.
Piping length max.
Piping length equivalent
Piping length chargeless
Additional refrigerant charge
Installation height difference max.
Max. intern unit level difference
Heat insulation
Defrost method
Defrost control
Capacity control method
Safety devices
Item
Standard
accessories
Quantity
Item
Standard
accessories
Quantity
Notes:
1. Nominal cooling capacities are based on:
2. Nominal heating capacities are based on:
Specifications
RZQ71C7V1B
50 m
See installation manual
4PW40417-1
Indoor temperature: 27.0°C DB/19.0°C WB
Outdoor temperature: 35.0°C DB
Equivalent refrigerant piping: 7.5 m
Level difference: 0 m
Indoor temperature: 20°C DB
Outdoor temperature: 7.0°C DB/6.0° C WB
Equivalent refrigerant piping: 7.5 m
Level difference: 0 m
RZQ100C7V1B
RZQ125C7V1B
1
Flare connection
9.52 mm
1
Flare connection
15.9 mm
3
Hole
26.0 mm
5 m
70 m
30 m
See installation manual 4PW34874-1
30.0 m
0.50 m
Both liquid and gas pipes
Pressure equalising
Sensor for outdoor heat exchanger temperature
Inverter controlled
High pressure switch
Fan motor thermal protector
Fuse
Tie-wraps
2
Installation manual
1
Specifications
RZQ140C7V1B
75 m
95 m
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents