How To Change The Field Settings With The Wireless Remote Controller - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
2.2
How to Change the Field Settings with the Wireless
Remote Controller
Optional
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed.
accessories
Refer to OH08-1 or the installation manual (optional handbook) for each optional accessory.
Wireless remote
The illustration below shows the wireless remote controller.
controller
Setting
To set the field settings, you have to change:
To change the field settings, proceed as follows:
Test Operation
Mode No.
Field setting mode
RESERVE button
First code No.
Second code No.
"Mode No."
"First code No."
"Second code No.".
Step
Action
1
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the "Field setting mode".
2
Press the MODE button to select the desired "Mode No.".
3
Press the UP button to select the "First code No.".
4
Press the DOWN button to select the "Second code No."
5
Press the RESERVE button to set the present settings.
6
Press the INSPECTION/TEST button to return to the "Normal mode".
Field Settings
UP button
DOWN button
MODE button
INSPECTION/TEST button