Removal Of Propeller Fan And Fan Motor - Daikin SkyAir Service Manual

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
1.2

Removal of Propeller Fan and Fan Motor

Procedure
Step
Remove the front panel 2,
following the procedure
indicated at "Removal of
Outside Panels and
Related Parts".
1. Remove the propeller fan
Remove the four
1
screws that fix the
discharge grille.
Remove from four
hooks at upper and
lower side and then
remove the discharge
grille.
Remove the fan setting
2
nut that fixes the
propeller fan.
3
* Remove the top
panel, following the
procedure indicated
at "Removal of
Outside Panels and
Related Parts".
2. Remove the fan motor
1
Remove the connector
for the fan motor from
the printed wiring board
(PWB). (Refer to *1)
Remove the three
2
clamps which fix the
lead wire. (Three hooks
of partition plate)
Remove the three
3
screws of the front
panel and then pull lead
wire frontward.
4
Pull out the fan motor,
after removing the four
fixing bolts.
Removal Procedure
Warning
Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Procedure
Propeller fan
Hooks
Fan setting nut
Hooks
Discharge grille
Connector for fan motor (X106A)
Clamp
Four bolts
RZQ71C7, RZQS71·100C7V1B
Points
In case of removing the
connector, do not pull the
lead wire. Hold the
connector part and push the
hook.
Lead wire
Propeller fan
Precaution for the motor
installation
Be sure to fix the lead wire of
the motor. Otherwise the
lead wire might be entangled
with the motor and causes
failure.