Field Settings
2.12 I-Demand Function
Purpose
Set a limitation towards the power consumption from the system.(e.g. budget control, limit
power consumption during peak moments,..)
Setting
3 different demand setting can be selected by using terminal X801M:
108
→
Demand 1
Close contact between COM and contact 1
→
Demand 2
Close contact between COM and contact 2
→
Demand 3
Close contact between COM and contact 3
Power supply connector
(on outdoor PCB X77A)
DS1
ON
OFF
1 2 3 4
X800M
X801M
3
2
1
LNOP COM
3
2
1
LNOP
SiBE28-804
Transmission connector
(on outdoor PCB X6A)
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter
X801M
COM
Test Operation