Parameters Setting - Smartgen HGM9560 User Manual

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

9 PARAMETERS SETTING

CAUTION: Please change the controller parameters when generator is in standby mode
only (e. g. configurable input, configurable output, various delay), otherwise, alarming to stop
and other abnormal conditions may happen.
NOTE: Maximum set value must over minimum set value in case that the condition of too
high as well as too low will happen.
NOTE: When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must less
than setting; when setting the minimum value, the return value must over setting.
NOTE: Configurable input could not be set as same items; otherwise, there are abnormal
functions. However, the configurable output can be set as same items.
HGM9560 Bus Tie Mains Parallel Unit
HGM9560 BUS TIE MAINS PARALLEL UNIT
ISSUE 2013-12-30
Version 1.0
Page 38 of 51

Advertisement

Table of Contents
loading

Table of Contents