9 PARAMETERS SETTING
CAUTION: Please change the controller parameters when generator is in standby mode
only (e. g. configurable input, configurable output, various delay), otherwise, alarming to stop
and other abnormal conditions may happen.
NOTE: Maximum set value must over minimum set value in case that the condition of too
high as well as too low will happen.
NOTE: When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must less
than setting; when setting the minimum value, the return value must over setting.
NOTE: Configurable input could not be set as same items; otherwise, there are abnormal
functions. However, the configurable output can be set as same items.