Smartgen HGM9560 User Manual page 32

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

No.
Items
11
Sync Gain
12
Sync Stability
13
kW Control Gain
kW
14
Stability
15
Sync Volt Gain
16
Sync Volt Stability
17
kvar Control Gain
kvar
18
Stability
19
MSC Number
Too Few Modules
20
Action
21
Baud Rate
Scheduled
22
PCT
Scheduled
23
PCT
24
Load Mode Control (0-2)
Output
25
Power
Reactive
26
Control
Reactive
27
Control Value
28
Min Start Sets
29
Not Reached Act
Request
30
Delay
HGM9560 Bus Tie Mains Parallel Unit
HGM9560 BUS TIE MAINS PARALLEL UNIT
Parameters
(0-500)
(0-2000)
(0-500)
Control
(0-2000)
(0-500)
(0-2000)
(0-500)
Control
(0-2000)
(1-32)
(0-2)
(0-3)
Run
(0-100)%
Stop
(0-100)%
Active
(0-100.0)%
Power
(0-1)
Power
(0-100.0)%
(1-32)
(0-2)
Start
(0-3600)s
Defaults
Action Type:
0:Warn;1:Trip.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
20
Adjust and control after paralleling.
20
Adjust and control after paralleling.
20
Adjust and control before paralleling.
20
Adjust and control before paralleling.
2
Action Type:
1
0:No Action;1:Warn;2:Trip.
0:500KBit/s;1:250KBit/s;
1
2:125KBit/s;3:50KBit/s.
Schedule the load value of other genset
80
when start on demand.
Schedule the load value of other genset
50
when start on demand.
0:Bus Control;1:Mains Control;
0
2:Load Control.
30.0
Used for load control.
0
0:kvar;1:PF
8.0
Used for load control.
1
When the controller does not detect the
1
Min Start Sets during the preset delay,
it will send corresponding alarm signal
according to the action type.
120
Action Type:
0:No Action; 1:Warn; 2:Trip.
ISSUE 2013-12-30
Description
Version 1.0
Page 32 of 51