Smartgen HGM9560 User Manual page 25

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

NO.
Functions
voltage sensing input
Genset
47
voltage sensing input
Genset N-wire input
48
Mains
CT
49
sensing input
Mains
CT
50
sensing input
Mains
CT
51
sensing input
Mains CT COM
52
53
Bus Current
54
55
Aux. input 8
NOTE: USB ports in controller rear panel are configurable parameter ports, user can directly
program controller via PC.
HGM9560 Bus Tie Mains Parallel Unit
HGM9560 BUS TIE MAINS PARALLEL UNIT
Cable
Size
C-phase
2
1.0mm
2
1.0mm
A-phase
2
1.5mm
B-phase
2
1.5mm
C-phase
2
1.5mm
2
1.5mm
2
1.5mm
2
1.5mm
2
1.0mm
ISSUE 2013-12-30
recommended).
Connected to C-phase of genset (2A fuse is
recommended).
Connected to N-wire of genset.
Externally connected to secondary coil of current
transformer (rated 5A).
Externally connected to secondary coil of current
transformer (rated 5A).
Externally connected to secondary coil of current
transformer (rated 5A).
See following section entitled Installation.
Externally connected to secondary coil of Bus CT
A-phase (rated 5A).
Ground
connected
active (B-)
Remark
is
Details see form 3.
Version 1.0
Page 25 of 51