Smartgen HGM9560 User Manual page 37

Bus tie mains parallel unit
Hide thumbs Also See for HGM9560:
Table of Contents

Advertisement

19
Reserved
20
Reserved
21
Inhibit Alarm Stop
22
Aux Instrument Mode
23
Reserved
24
Reset Maintenance
25~27
Reserved
Remote Start
28
(On Load)
Remote Start
29
(Off Load)
30
Aux. Manual Start
Remote Start
31
(On Demand)
Remote Start
32
(Island)
33
Simulate Stop key
34
Simulate Manual key
35
Reserved
36
Simulate Auto key
37
Simulate Start key
38
Simulate B-Load key
39
Simulate M-Load key
40~44
Reserved
45
Simulate Mains Normal
46
Simulate Mains Abnormal
47
Alternative Config 1
48
Alternative Config 2
49
Alternative Config 3
50
Reserved
HGM9560 Bus Tie Mains Parallel Unit
HGM9560 BUS TIE MAINS PARALLEL UNIT
All shutdown alarms are prohibited except emergence
stop.(Means battle mode)
All outputs are prohibited in this mode.
Controller will set maintenance time and date as default
when input is active.
In Auto mode, when the input is active, genset can be
started and with load after genset is OK; when the input
is inactive, genset will stop automatically.
In Auto mode, when the input is active, genset can be
started and without load after genset is OK; when the
input is inactive, genset will stop automatically.
In Auto mode, when the input is active, genset will start
automatically; when the input is inactive, genset will stop
automatically
In Auto mode, when the input is active, all genset that
need to be parallel will start according to the priority and
calling other generator according to the load.
In Auto mode, when the input is active, genset will start
automatically; genset will take load when it is normal
running while mains off load. when the input is inactive,
mains will take load while genset off load and stop
automatically.
An external button (not self-locking) can be connected
and pressed as simulate panel.
An external button (not self-locking) can be connected
and pressed as simulate panel.
In Auto mode, when the input is active, mains is normal.
In Auto mode, when the input is active, mains is
abnormal.
Users can set different parameters to make it easy to
select current configuration via input port.
ISSUE 2013-12-30
Version 1.0
Page 37 of 51