REMKO Smart-Control Touch
Default settings for SQW Package Cologne
Menu item
Activate heat pump
Auxiliary heat generator
Domestic hot-water heating
Storage tank set temperature
Hot water circulation
Circulation type
Unmixed circuit
Heating circuit mode
Heating-curve base point
Standard inlet temperature
Standard outside temperature
1st mixed circuit
Heating circuit mode
Heating-curve base point
Standard inlet temperature
Standard outside temperature
2nd mixed circuit
Heating circuit mode
Heating-curve base point
Standard inlet temperature
Standard outside temperature
3rd mixed circuit
Heating circuit mode
Heating-curve base point
Standard inlet temperature
Standard outside temperature
Setpoint increase
Separate cooling buffer
Building time constant
The parameters must still be adjusted by the customer in accordance with the specifications!
68
Parameter
Activated/Deactivated
Activated/Deactivated
Activated/Deactivated
"40°C - 65°C"
Activated/Deactivated
Impulse
Activated/Deactivated
Heating curve
"15 °C - 35 °C"
"40°C - 90 °C"
"0 °C - 20 °C"
Activated/Deactivated
Heating curve
"15 °C - 25 °C"
"28 °C - 90 °C"
"0 °C - 20 °C"
Activated/Deactivated
Heating curve
"15 °C - 25 °C"
"28 °C - 90 °C"
"0 °C - 20 °C"
Activated/Deactivated
Heating curve
"15 °C - 25 °C"
"28 °C - 90 °C"
"0 °C - 20 °C"
0 - 10 k
Activated/Deactivated
0 h - 100 h
Factory setting
Activated
Deactivated
Deactivated
45 °C
Deactivated
Deactivated
Activated
Activated
30 °C
55 °C
20 °C
Activated
Activated
20 °C
35 °C
20 °C
Activated
Activated
20 °C
35 °C
20 °C
Activated
Activated
20 °C
35 °C
20 °C
5 k
Deactivated
10 h