Tyco DV-5 General Description Manual

Tyco DV-5 General Description Manual

Preaction system with dv-5 deluge valve single interlock, supervised wet pilot actuation 1-1/2 thru 8 inch (dn40 thru dn200)
Hide thumbs Also See for DV-5:

Advertisement

Quick Links

Preaction System with DV-5 Deluge Valve
Single Interlock, Supervised — Wet Pilot Actuation
1-1/2 thru 8 Inch (DN40 thru DN200)
General
Description
The DV-5 Supervised Single Interlock
Preaction System with Wet Pilot Ac-
tuation (Refer to Figure 1) utilizes au-
tomatic sprinklers and a supplemental
detection system. The supplemental
detection system is comprised of wet
pilot lines and pilot sprinklers. Actua-
tion of the detection system automati-
cally operates (releases) the DV-5 Del-
uge Valve, allowing water to flow into
the sprinkler piping system and to be
discharged from any sprinklers that
may be open.
In accordance with the requirements
of the National Fire Protection Asso-
ciation, a preaction system employing
more than 20 automatic sprinklers is
to have the sprinkler piping automati-
cally supervised to monitor the overall
integrity of the system. In the case of
a Supervised Single Interlock Preac-
tion System, a Riser Check Valve (that
does not require the use of priming wa-
ter) provides an air check so that the
system can be automatically pressur-
ized with a nominal supervisory air or
nitrogen pressure of 10 psi (0,69 bar). A
supervisory low pressure alarm switch
that is set to transfer its contacts at
nominally 5 psi (0,34 bar), on decreas-
ing pressure, is utilized to indicate
whether there are any abnormal leaks
in the sprinkler system piping. Loss of
air pressure from the system as a re-
sult of a damaged sprinkler or broken
piping will not cause the DV-5 Valve to
open — the air pressure is for supervi-
sory alarm only.
Typically, the system designer selects
the detection components for a single
interlock preaction system that will re-
spond to a fire sooner than the auto-
matic sprinklers. Consequently, the
system will experience a minimal de-
lay in water delivery over that for a wet
pipe sprinkler system because the sys-
tem will have essentially filled with wa-
ter before a sprinkler operates. In the
case of wet pilot actuation, the system
designer selects wet pilot sprinklers
that will operate sooner than the auto-
matic sprinklers chosen for use on the
sprinkler piping.
Page 1 of 14
Supervised single interlock preaction
systems are generally used to protect
areas where there is danger of serious
water damage that might result from
damaged automatic sprinklers or pip-
ing. Typically, such areas include com-
puter rooms, storage areas for valuable
artifacts, libraries, and archives.
Single interlock preaction systems are
also effectively used to protect prop-
erties where a pre-alarm of a possible
fire condition may allow time for fire ex-
tinguishment by alternate suppression
means, prior to a sprinkler discharge.
In the event the fire cannot otherwise
be extinguished, the preaction sprinkler
system will then perform as the primary
fire protection system.
The DV-5 Deluge Valve (described in
Technical Data Sheet TFP1305) is a
diaphragm style valve that depends
upon water pressure in the Diaphragm
Chamber to hold the Diaphragm closed
against the water supply pressure.
When the DV-5 Valve is set for service,
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system's main control
valve, such as an O.S.&Y. gate valve or
butterfly valve (Fig. 1).
JULY 2014
Worldwide
www.tyco-fire.com
Contacts
Opening of a pilot sprinkler, releas-
es water from the Diaphragm Cham-
ber faster than it can be replenished
through the 1/8 inch (3,2 mm) restric-
tion provided by the Model ASV-1
Automatic Shut-Off Valve in the dia-
phragm supply connection (Item 5 -
Fig. 3A, also described in Technical
Data Sheet TFP1384). This results in a
rapid pressure drop in the Diaphragm
Chamber to below the valve trip point.
The water supply pressure then forces
the Diaphragm open, permitting water
to flow into the system piping, as well
as through the Alarm Port to actuate
the system alarms.
As water flows into the system, the pi-
lot chamber of the Model ASV-1 Auto-
matic Shut-Off Valve (Item 5 - Fig. 3A)
becomes pressurized and the ASV-1
automatically shuts off the diaphragm
chamber supply flow to the DV-5 Di-
aphragm Chamber. Shutting off the
diaphragm chamber supply flow pre-
vents the DV-5 Diaphragm Chamber
from becoming re-pressurized, there-
by preventing inadvertent closing of the
DV-5 during a fire (as may be the case
if an actuation device other than a pi-
lot sprinkler were to be closed after its
initial operation, for example a remote
manual control station).
Continued on Page 4
TFP1410

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DV-5 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco DV-5

  • Page 1 DV-5 during a fire (as may be the case ter before a sprinkler operates. In the inlet side of the system’s main control...
  • Page 2 TFP1410 Page 2 of 14 DV-5 Deluge Valve System Drain Valve (N.C.) Automatic Supervisory Air/Nitrogen Supply Main Control Valve (N.O.) Main Drain Valve (N.C.) (Shown at Rear of Valve) Supervisory Low Pressure Alarm Diaphragm Chamber Supply Switch Control Valve (N.O.)
  • Page 3 TFP1410 Page 3 of 14 DV-5 Deluge Valve Diaphragm Chamber Pressure Automatic Supervisory Air/Nitrogen Gauge (Shown at Front of Valve) Supply Main Control Valve (N.O.) System Drain Valve (N.C.) Supervisory Low Pressure Alarm Diaphragm Chamber Supply Switch Control Valve (N.O.) Main Drain Valve (N.C.)
  • Page 4: Technical Data

    Table A as a (PS10-2) DV-5 function of the minimum water sup- ply pressure to the DV-5 Valve for an The following items are included in the Riser Check Valve equivalent length (pipe plus fittings) of...
  • Page 5 Deluge Valve Port identi cation. galvanized (Standard Order). Route all Tubing to Drip Funnel, CH: Common Hardware. Item 14. FIGURE 3A (1 OF 3) 1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM WITH WET PILOT ACTUATION TRIM EXPLODED VIEW...
  • Page 6 Deluge Valve Port identi cation. galvanized (Standard Order). Route all Tubing to Drip Funnel, CH: Common Hardware. Item 14. FIGURE 3A (2 OF 3) 3 INCH (DN80) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM WITH WET PILOT ACTUATION TRIM EXPLODED VIEW...
  • Page 7 (Standard Order). Route all Tubing to Drip Funnel, CH: Common Hardware. Item 15. FIGURE 3A (3 OF 3) 4, 6, AND 8 INCH (DN100, DN150 AND DN200) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION SYSTEM WITH WET PILOT ACTUATION TRIM EXPLODED VIEW...
  • Page 8 MAIN DRAIN 1/2 INCH NPT VALVE SHOWN OPEN) CONNECTION CONNECTION FROM (SIZED PER TABLE) WATER SUPPLY FIGURE 3B 1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 SUPERVISED SINGLE INTERLOCK PEACTION WITH WET PILOT ACTUATION TRIM OPERATIONAL COMPONENTS SEMI-PREASSEMBLED TRIM EXPLODED ARRANGEMENT...
  • Page 9: Left View

    (406,4) (539,8) (266,7) (933,5) (44,5) (273,1) (269,9) (158,8) (181,0) (181,0) (927,1) (134,0) MINIMUM CLEARANCE. LEFT VIEW FRONT VIEW FIGURE 4 1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 SUPERVISED SINGLE INTERLOCK PREACTION WITH WET PILOT ACTUATION TRIM NOMINAL INSTALLATION DIMENSIONS...
  • Page 10 Interpolation between data points is permitted. TABLE A 1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 WET PILOT DESIGN CRITERIA FOR UP TO 500 FEET OF EQUIVALENT LENGTH OF PILOT LINE (PIPE PLUS FITTINGS) NOTES: Wet Pilot Lines must be main- • Model G16AC812 (self-contained)
  • Page 11: Installation

    The DV-5 Valve must be installed in a ambient must be replaced. Step 13. Conduit and electrical con- readily visible and accessible location. Step 7. Open the Diaphragm Chamber...
  • Page 12 103 feet of 8 inch Sch. 30 Pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 gpm. GRAPH A DELUGE AND CHECK VALVE COMBINATION* NOMINAL PRESSURE LOSS VERSUS FLOW *DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve **1-1/2 Inch DV-5 Deluge combined with 2 Inch Model CV-1FR Riser Check Valve...
  • Page 13: Care And Maintenance

    NOTE: In order to prevent the pos- Step 3. Verify that the DV-5 Valve has in addition to any specific requirements sibility of a subsequent operation of tripped, as indicated by the flow of wa-...
  • Page 14 8 Inch ....P/N 59-590-1-080 NOTE: For 1-1/2 inch (DN40) risers, use the 2 Inch (DN50) Riser Check Valve. GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved.