Tyco DV-5a Manual

Tyco DV-5a Manual

Automatic water control valve electric/electric double interlock preaction fire protection systems 1 1/2 inch to 8 inch dn40 to dn200
Hide thumbs Also See for DV-5a:

Advertisement

Quick Links

DV-5a Automatic Water Control Valve Electric/
Electric Double Interlock Preaction Fire Protection
Systems 1 1/2 Inch to 8 Inch (DN40 to DN200)
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp1466
General
Description
The TYCO DV-5
Automatic Water
a
Control Valves are diaphragm type
valves that can be used in double inter-
lock preaction fire protection systems.
When properly trimmed, the double
seat design of the DV-5
a
provides actuation of fire alarms upon
system operation.
The diaphragm style design of the
DV-5
Valve allows external resetting,
a
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5
features internal and exter-
a
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5
rosive atmospheres associated with
many types of industrial processing
plants and outdoor installations.
The DV-5
Valves are offered with the
a
Page 1 of 18
End Connection
Inlet
Outlet
Thread
Thread
Groove
Groove
Valve also
Flange
Groove
Flange
Flange
DV-5
Valve and separately ordered
a
semi-assembled trim shown in Figures
6 and 7, or, for ease of installation, with
DV-5
Valve completely trimmed with or
a
without a System Main Control Valve.
Double interlock preaction systems are
designed for use in applications, such
as refrigerated areas, requiring the
maximum degree of protection against
in cor-
inadvertent flooding of the sprinkler
a
system piping. In order for a double
interlock preaction system to automat-
ically activate, two independent events
must occur. First, the electric detection
SEPTEMBER 2022
Worldwide
Available End Connections and Weights — lb/(kg)
Nominal Valve Size
1 1/2
2
3
(40)
(50)
(80)
26
25
N/A
(11,8)
(11,3)
25
25
60
(11,3)
(11,3)
(27,2)
66
N/A
N/A
(30,0)
72
N/A
N/A
(32,7)
system must operate, and secondly,
an automatic sprinkler on the system
piping must operate. Typically, the
electric detection system is designed to
operate before any automatic sprinkler.
Operation of just the electric detection,
or just the opening of a sprinkler will
not allow the DV-5
permit water to flow into the normally
dry sprinkler system piping. However,
operation of just the electric detec-
tion system or the opening of a sprin-
kler (loss of system air pressure) will
result in a supervisory alarm to notify
the building occupants of a condition
www.tyco-fire.com
Contacts
ANSI Inches
(DN)
4
6
165,1
(100)
(150)
mm
N/A
N/A
N/A
95
177
177
(43,1)
(80,3)
(80,3)
106
190
N/A
(48,1)
(86,2)
116
204
N/A
(52,6)
(92,5)
Valve to open and
a
TFP1466
8
(200)
N/A
327
(148,3)
346
(157,0)
365
(165,6)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DV-5a and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco DV-5a

  • Page 1 Worldwide www.tyco-fire.com Contacts DV-5a Automatic Water Control Valve Electric/ Electric Double Interlock Preaction Fire Protection Systems 1 1/2 Inch to 8 Inch (DN40 to DN200) IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
  • Page 2 TFP1466 Page 2 of 18 Nominal Valve Size ANSI Inch (DN) Item Description Qty. 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) Valve Body Diaphragm 545000020 545000020 545000030 545000040 545000060 545000080 Diaphragm Cover Hex Bolt, Short 545100001 545100001 545100002...
  • Page 3 TFP1466 Page 3 of 18 Port Sizes, NPT Inch per ANSI B1.20.1 Port Port Description 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) Diaphragm Chamber Supply Water Supply Pressure & Alarm Test Alarm Actuation Automatic Drain Valve System Drain Main Drain 1 1/4...
  • Page 4: Technical Data

    TFP1466 Page 4 of 18 needing attention so as to avoid inad- Valve Trim DIMENSIONS SHOWN vertent flooding of the system piping. The maximum pressure rating for the ARE APPLICABLE TO Electric/Electric Double Interlock Pre- ALL END CONNECTION A solenoid valve is used in the Elec- action Trim is dependent on separately CONFIGURATIONS tric/Electric Actuation to hold the DV-5...
  • Page 5: Operation

    Electric Actuation (see Figure 4) trips the Model MRA-1 Manual Reset Actua- Model MRA-1 Manual Reset Actuator. tor opens to constantly vent the DV-5 The TYCO DV-5 Valve is a diaphragm Tripping the MRA-1 releases water from Diaphragm Chamber to "hydraulically...
  • Page 6 24 VOLTS DC) CROSS-ZONE DELUGE VALVE RELEASING PANEL SYSTEM (AUTOMATIC SHUT-OFF VALVE DRAIN CONTROL UNIT (NORMALLY OPEN) WITH BATTERY SYSTEM DRAIN VALVE WATERFLOW BACK-UP) DV-5A (NORMALLY CLOSED) PRESSURE VALVE ALARM AUTOMATIC SWITCH MAIN POWER AIR/NITROGEN DRAIN VALVE SUPPLY SUPPLY (NORMALLY...
  • Page 7: Installation

    12 in. RCDS-1 Releasing Circuit Switch, or (300 mm) below the Drip Funnel. DV-5A Automatic Water Control Valves equivalent. The RCDS-1 provides for a are designed to be used in freshwater Step 6. Suitable provision must be temporary disconnect (de-energized) of systems.
  • Page 8 Manual Control Station (M) Perform Steps 1 through 20 when ini- drain tube, slowly close the operating tially setting the TYCO DV-5 Valve, NOTICE lever by pushing it up. Do not close the after an operational test of the fire pro- hinged cover at this time.
  • Page 9 TFP1466 Page 9 of 18 Assemble in order 1-1/2" (DN40) AND 2" (DN50) from A to L VALVES ONLY Notes: 1. Port Connections P1 through P7 are described in Figure 2. 2. External Trim Connections C1 through C5 are described in Figure 8. 3.
  • Page 10 Item A7 is provided as 52-287-1-124 described in Technical Data Sheet TFP2180 4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A10 are sepa- rately ordered, as applicably related to valve size. Water Pres- sure Gauges for EMEA valve trim are also separately ordered.
  • Page 11 — — DV-5 VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS WATERFLOW PRESSURE ALARM SWITCH, 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 DOUBLE CONTACTS (APAC)
  • Page 12 TFP1466 Page 12 of 18 Nominal Inches Valve (mm) Size ANSI Inches (DN) 1 1/2 15.7 16.0 10.2 8.02 (40) (71) (246) (249) (399) (406) (188) (259) (204) (31) 15.7 16.0 10.2 8.09 (50) (71) (246) (249) (399) (406) (188) (259) (205) (74)
  • Page 13: Care And Maintenance

    TFP1466 Page 13 of 18 Care and sprinkler systems be inspected, tested, debris in the check valve seal area), a and maintained by a qualified Inspec- deluge valve such as the DV-5 could Maintenance tion Service in accordance with the inadvertently trip, if its water supply NFPA and any applicable standards pressure is quickly restored.
  • Page 14 TFP1466 Page 14 of 18 Item Description Item Description External Trim Connections DV-5 Valve Manual Reset Actuator Diaphragm Supply Connection System Main Control Valve Diaphragm Supply Valve Water Motor Alarm Connection Waterflow Pressure Switch Diaphragm Supply Strainer Air Supply Connection Main Drain Valve Inverted Flare Shut-Off Valve Waterflow Pressure Alarm Switch...
  • Page 15 TFP1466 Page 15 of 18 Electric/Electric Actuation to normal. To perform internal valve inspection between Steps 4 and 5 of the Valve System Operation Procedure Step 7. Close the System Shut-Off Setting Procedure remove the Dia- Proper operation of the DV-5 Valve for Valve (W) after the system air pressure phragm cover as follows:...
  • Page 16 8 in. (DN200) ....550021580 end connection with assembled gal- Use only TYCO replacement fasteners Flange x Grooved ANSI vanized EMEA, Double Interlock Pre- 3 in.
  • Page 17 TFP1466 Page 17 of 18 Upon request, valves can be provided with Separate DV-5 Valves without Trim Flange x Flange ANSI flange drilling per JIS B 2210 or AS 2129. In 3 in. (DN80) ....550121530 See Table A for flange drilling 4 in.
  • Page 18 TFP1466 Page 18 of 18 DV-5 Valve Trim Accessories DV-5 Valve Replacement Parts DV-5 Valve Trim Replacement (for separately ordered valve trim) Specify: (Description) for use with Parts (specify size) DV-5 Automatic Water Specify: (Specify Accessory Descrip- Specify: (Description) for use with tion), P/N (specify): Control Valve, P/N (See Figure 1) DV-5...
  • Page 19: General Description

    Worldwide www.tyco-fire.com Contacts DV-5 Appendix Poster Printing Instructions General General Description Description The appendix found at the end of this The appendix found at the end of this document provides valve setting and document provides valve setting and Valve Setting Procedure Valve Setting Procedure 7.
  • Page 20 System Drain Valve (E) to relieve air pressure at Low Air Pressure Alarm Technical Data Sheet TFP1466. If problems occur, consult full document. Switch (U). Verify DV-5a Valve operates as is indicated by discharging water from System 11. Inspect Electric/Electric actuation drain connection from Manual Control Station (M) and Drain Valve (E) and Automatic Drain Valve (F).