Setting The Dil Switches - Festo CPV GE-CO2-8 Series Electronic Manual

Cpv valve terminal with direct connection
Hide thumbs Also See for CPV GE-CO2-8 Series:
Table of Contents

Advertisement

1. Installation

1.2.2 Setting the DIL switches

Festo P.BE-CP-CO2-EN en 0107NH
When the switch module has been removed, you will see two
DIL switches in it (Fig. 1/3).
You can set the following parameters with the DIL switches:
Baud rate
Extension to the CP system
Station number
Proceed as follows:
1. Switch off the operating voltage.
2. Remove the switch module (chapter 1.2.1).
3. Set the baud rate (4-position DIL switch, elements 1...2).
4. Set the extension to the CP system (4-position DIL switch,
elements 3...4).
5. Assign an unused station number to the CPV Direct.
Set the desired station number (8-position DIL switch,
elements 1...7).
6. Fit the switch module (chapter 1.2.1).
1-7