Huawei OceanStor Dorado V3 Series Parts Replacement page 58

Hide thumbs Also See for OceanStor Dorado V3 Series:
Table of Contents

Advertisement

OceanStor Dorado V3 Series
Parts Replacement
l
l
Procedure
Step 1 Perform a pre-replacement check.
Check whether there is a redundant fan module and whether the Running/Alarm indicator of
the fan module is steady green, as shown in
different components, see
Enclosure.
Figure 4-51 Running/Alarm indicator on a fan module
You can perform replacement only when a redundant fan module exists and the redundant fan
module is working properly.
Step 2 Wear an ESD wrist strap.
Step 3 Remove a fan module, as shown in
1.
2.
Issue 05 (2019-01-30)
ESD bag
Labels
Running/Alarm Indicators on a Dorado6000 V3 Controller
Press the latch on the panel to open the panel.
Press the latches on the fan module to pull out the fan module.
Copyright © Huawei Technologies Co., Ltd.
Figure
4-51. For details about the indicators on
Figure
4-52.
4 Replacing CRUs
50