SMC Networks PF3A703H-L Operation Manual page 55

Digital flow switch
Hide thumbs Also See for PF3A703H-L:
Table of Contents

Advertisement

●When the set value and hysteresis of the switch output (OUT1/2) is set within the zero-cut range.
The operating point of the switch output will be changed, depending on the zero-cut setting value.
However, please note that the set value and hysteresis of the switch output will not be changed.
To maintain the on-off point, set the value and hysteresis without the zero cut-off range.
<Example: PF3A703H (3000 L/min type>
Common setting
Output mode
Switch operation
Set value (P_1)
Hysteresis (H_1)
Initial setting
Zero cut-off setting CUt: 1.0 (displays 0 for a value below 30 L/min)
Switch ON point
Switch OFF point
~Condition when the operating point of hysteresis (H_1) is changed~
•The zero-cut setting CUt: 1.0 will be changed to CUt: 2.0. (0 will be displayed for a value below 60 L/min)
Switch ON point
Switch OFF point
~Condition when the operating point of the set point (P_1) and hysteresis (H_1) is changed~
•The zero-cut setting CUt: 1.0 will be changed to CUt: 3.0. (0 will be displayed for a value below 90 L/min)
Switch ON point
Switch OFF point
Hysteresis mode
Normal output
80
30
80 L/min or more
Below 50 L/min
Change the zero cut-off setting
The set value (P_1) and hysteresis (H_1)
cannot be changed.
80 L/min or more
Below 60 L/min (0 is displayed)
90 L/min or more
Below 90 L/min (0 is displayed)
-54-