[Window comparator mode]
The Flow switch turns on within a set flow range (from P1L to P1H). Set P1L, the lower limit of the switch
operation, and P1H, the upper limit of the switch operation and WH1 (hysteresis) following the instructions
given above.
When reversed output is selected, the main screen displays [n1L] and [n1H].
[Accumulated output mode]
Set each P1 (set value), referring to setting method of page 27.
(When reversed output is selected, the main screen displays [n1]).
Refer to the switch output modes list for the relationship between the set values and operation (page 35).
Setting of the normal/ reverse output switching and hysteresis/window comparator mode switching are performed using the
function selection mode [F 1] OUT1 setting.
-28-
No.PF※※-OMX0002