SMC Networks PF3A703H-L Operation Manual page 53

Digital flow switch
Hide thumbs Also See for PF3A703H-L:
Table of Contents

Advertisement

●Settable flow range when [L] is selected by the units selection function
Zero cut-off
Zero cut-off
set value
range
0.0
0%F.S.
1.0
0 to 1%F.S.
2.0
0 to 2%F.S.
3.0
0 to 3%F.S.
4.0
0 to 4%F.S.
5.0
0 to 5%F.S.
6.0
0 to 6%F.S.
7.0
0 to 7%F.S.
8.0
0 to 8%F.S.
9.0
0 to 9%F.S.
10.0
0 to 10%F.S.
: The zero-cut range of the accumulated value and accumulated pulse value should be 1% F.S. or more. However, please note that if
the zero-cut set value is 0.0, any value below 1% F.S. will be cut.
: When setting the flow value and hysteresis within zero cut-off settable range, the on-off point varies depending on the settable range.
For details, please refer to switch output (OUT) value and hysteresis are set within Zero cut-off range (page 54).
PF3A703H
0 to 3150 L/min
30 to 3150 L/min
(Displays 0 when the
value is below 30 L/min)
60 to 3150 L/min
(Displays 0 when the
value is below 60 L/min)
90 to 3150 L/min
(Displays 0 when the
value is below 90 L/min)
120 to 3150 L/min
(Displays 0 when the
value is below 120 L/min)
150 to 3150 L/min
(Displays 0 when the
value is below 150 L/min)
180 to 3150 L/min
(Displays 0 when the
value is below 180 L/min)
210 to 3150 L/min
(Displays 0 when the
value is below 210 L/min)
240 to 3150 L/min
(Displays 0 when the
value is below 240 L/min)
270 to 3150 L/min
(Displays 0 when the
value is below 270 L/min)
300 to 3150 L/min
(Displays 0 when the
value is below 300 L/min)
-52-
Displayable flow range
PF3A706H
0 to 6300 L/min
60 to 6300 L/min
(Displays 0 when the
value is below 60 L/min)
120 to 6300 L/min
(Displays 0 when the
value is below 120 L/min)
180 to 6300 L/min
(Displays 0 when the
value is below 180 L/min)
240 to 6300 L/min
(Displays 0 when the
value is below 240 L/min)
300 to 6300 L/min
(Displays 0 when the
value is below 300 L/min)
360 to 6300 L/min
(Displays 0 when the
value is below 360 L/min)
420 to 6300 L/min
(Displays 0 when the
value is below 420 L/min)
480 to 6300 L/min
(Displays 0 when the
value is below 480 L/min)
540 to 6300 L/min
(Displays 0 when the
value is below 540 L/min)
600 to 6300 L/min
(Displays 0 when the
value is below 600 L/min)
PF3A712H
0 to 12600 L/min
120 to 12600 L/min
(Displays 0 when the
value is below 120 L/min)
240 to 12600 L/min
(Displays 0 when the
value is below 240 L/min)
360 to 12600 L/min
(Displays 0 when the
value is below 360 L/min)
480 to 12600 L/min
(Displays 0 when the
value is below 480 L/min)
600 to 12600 L/min
(Displays 0 when the
value is below 600 L/min)
720 to 12600 L/min
(Displays 0 when the
value is below 720 L/min)
840 to 12600 L/min
(Displays 0 when the
value is below 840 L/min)
960 to 12600 L/min
(Displays 0 when the
value is below 960 L/min)
1080 to 12600 L/min
(Displays 0 when the
value is below 1080 L/min)
1200 to 12600 L/min
(Displays 0 when the
value is below 1200 L/min)
No.PF※※-OMX0002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pf3a706h-lPf3a712h-lPf3a703hPf3a706hPf3a712h

Table of Contents