Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 98

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY
DISPLAY TEXT
INDOOR FAN (cont)
VFD IN REVERSE?
IDF VFD PARAMETERS
IDF VFD NOM. HP
IDF VFD VOLTAGE
IDF VFD NOM. FREQ
IDF VFD NOM. AMPS
IDF VFD NOM. RPM
IDF VFD MIN REF
IDF VFD MAX REF
VFD ACCEL. TIME
VFD DECEL. TIME
IDF VFD MAX AMPS
IDF VFD TIMEOUT
IDF VFD RESET DUR
VFD RFI FILTER
ECONOMIZER
ECON INSTALLED?
ECON MAX POS
ECON TRAVEL TIME
MINIMUM POSITION
CONFIGS
MIN POS@ MAX FAN
MIN POS SPEED 1
MIN POS DAMP 1
MIN POS SPEED 2
MIN POS DAMP 2
MIN POS SPEED 3
MIN POS DAMP 3
FREE COOL CONFIGS
LOW COOL SAT SP
HIGH COOL SAT SP
FREE COOL MAX OAT
FREE COOL MIN OAT
Table B — Settings Main Menu Layout (cont)
EXPANDED TEXT
IDF VFD Motor In Reverse
Indoor Fan VFD Settings Menu
IDF VFD Motor HP
IDF VFD Motor Volts
IDF VFD Motor Freq.
IDF VFD Motor Current
IDF VFD Motor Nom. RPM
IDF Danfoss Min Ref
IDF Danfoss Max Ref
IDF VFD Accel. Time
IDF VFD Decel. Time
IDF VFD Max Current
IDF Danfoss Comm. TO
IDF Danfoss Auto Reset
IDF Danfoss RFI Filter
Economizer Configurations Menu
Economizer Installed?
Econ Max Damper Position
Economizer Travel Time
Minimum Position Configurations
Menu
Econ Min at Max Fan Speed
Min Pos – User Speed 1
Min Pos – User Pos 1
Min Pos – User Speed 2
Min Pos – User Pos 2
Min Pos – User Speed 3
Min Pos – User Pos 3
Free Cooling Specific
Configurations Menu
Low Free Cool SAT Setpnt
High Free Cool SAT Setpnt
Free Cooling Max OAT
Free Cooling Min Temp
RANGE
UNITS
Yes/No
1 to 26
HP
50 to 1000
V
20 to 400
Hz
0.1 to 40
A
100 to 60000
rpm
0 to 65
Hz
0 to 65
Hz
1 to 1800
sec
1 to 1800
sec
0 to 655.35
A
1 to 600
sec
0 to 600
sec
On/Off
Yes/No
0 to 100
%
5 to 300
sec
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
40 to 80
°F
40 to 80
°F
0 to 90
°F
-30 to 70
°F
98
DEFAULT
POINT
No (sizes 04-12)
VFD1MDIR
Yes (sizes 14-26)
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
MOTPWRHP
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
MOTVOLT
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
60
MOTFREQ
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
MOTCUR
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
MOTNOMSP
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
0
MINREF
60
MAXREF
10
RAMPUP_T
10
RAMPDN_T
See VFD Motor
Default Configuration
Tables.
Table 35 (sizes 04-06)
VFD1MAXA
Table 42 (Vert. sizes
07-26)
Table 43 (Horz. Sizes
14-26)
30
CNT_TOUT
30
ARSTRT_T
On
RFIFILTR
No: no FIOP
ECONO
Yes: FIOP
100
DAMPMAX
150
ECONOTRV
30
MINP_MAX
0
MP_USPD1
0
MP_UPOS1
0
MP_USPD2
0
MP_UPOS2
0
MP_USPD3
0
MP_UPOS3
65
LCSASP
55
HCSASP
65
MAXFREET
0
MINFREET

Hide quick links: