Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 159

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

TABLE NAME
Occupied Cool Setpoint
Occupied Heat Setpoint
Unoccupied Cool Setpoint
Unoccupied Heat Setpoint
SET_PNT
Heat-Cool Setpoint Gap
SPT Offset Range (±)
Occupied SPRH Setpoint
Unoccupied SPRH Setpoint
TABLE NAME
Device Name:
Description:
Location:
Software Part Number:
CTLRID
Model Number:
Serial Number:
Reference Number:
The SystemVu controller is i-Vu
equipment and view files that organize the BACnet points for
the graphic page and property pages in i-Vu. The controller
supports single point linkage, proprietary i-Vu zoning linkage,
and the BACnet notification object for alarms.
POINT DESCRIPTION
A1 Loader Resets Count
Actual Cool Stage Active
Actual fan status
Actual Heat Stage Active
Alarm display info
Alarm Relay Resets Count
Alarm Relay Run Hours
Alarm Relay Starts
Alarm Reset Counts
Alarm Reset Resets Count
AQ Diff Low-IAQ OVERRIDE
AQ Differential High
AQ Differential Low
AQ DiffHigh-IAQ OVERRIDE
Average Occup. Cool Stp.
Average Occup. Heat Stp.
Average Occup. Zone Temp
Average Unocc. Cool Stp.
Average Unocc. Heat Stp.
Average Zone Temperature
BACKUP Preparation Time
BACnet device for IAQ
BACnet device for OAQ
BACnet device for OARH
BACnet device for OAT
BACnet device for RARH
BACnet device for RAT
BACnet device for SPRH
BACnet device for SPT
BACnet Device Macaddress
BACnet ID Number
APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
Table W — SETPOINT TABLE
DISPLAY NAME
Table X — CONTROL ID TABLE
DISPLAY NAME
48_50LC_
text string
text string
CESR131651-XX-XX
xxxxxxxxxxxxxxxxxx
xxxxxxxxxx
compatible and includes
®
Table Y — BACnet* AV Points List
POINT ACCESS
UNITS
READ ONLY
READ ONLY
R/W
READ ONLY
READ ONLY
READ ONLY
READ ONLY
hrs
READ ONLY
READ ONLY
READ ONLY
R/W
PPM
R/W
R/W
R/W
PPM
R/W
°F
R/W
°F
R/W
°F
R/W
°F
R/W
°F
R/W
°F
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RANGE
UNITS
55 to 80
°F
55 to 80
°F
65 to 95
°F
40 to 80
°F
2 to 10
^F
0 to 5
°F
0 to 100
%
0 to 100
%
RANGE
UNITS
When notification of alarms is turned off, this does not mean
the Alarm condition has been cleared. It just means the notifi-
cation of the alarm has been temporarily stopped. If the alarm
condition still exists after a delay, the notifications will start be-
ing sent again.
BACNET
BACNET
OBJECT NAME
rs_aldr
AV:7012
actcstgs
AV:194
idf_status
AV:190
acthstgs
AV:46
alarm_info
AV:14
rs_alm
AV:99
hour_alarm
AV:49
st_alm
AV:136
st_alrst
AV:137
rs_alrst
AV:100
aqd_low
AV:443
daq_high
AV:212
daq_low
AV:213
aqd_high
AV:442
lnk_ocsp
AV:264
lnk_ohsp
AV:266
lnk_aozt
AV:255
lnk_ucsp
AV:274
lnk_uhsp
AV:275
lnk_azt
AV:256
bkpreptm
AV:336
deviaq
AV:8001
devoaq
AV:8002
devoarh
AV:8004
devoat
AV:8003
devrarh
AV:8005
devrat
AV:8006
devsprh
AV:8028
devspt
AV:8007
bac_mac
AV:189
bac_id
AV:188
159
POINT NAME
DEFAULT
OCSP
78
OHSP
68
UCSP
85
UHSP
60
HCSP_GAP
5
SPTO_RNG
5
SPRH_OSP
55
SPRH_USP
55
POINT NAME
VALUE
CCN POINT
ID
RANGE
EQUIVALENT
0 to 65535
RS_ALDR
0 to 3
ACTCSTGS
0 to 100
IDF_STAT
0 to 2
ACTHSTGS
0 to 2
ALARM
0 to 65535
RS_ALM
0 to 999999
HR_ALM
0 to 999999
ST_ALM
0 to 999999
ST_ALRST
0 to 65535
RS_ALRST
0 to 5000
AQD_LOW
0 to 5000
DAQ_HIGH
0 to 5000
DAQ_LOW
0 to 5000
AQD_HIGH
55 to 80
LNK_OCSP
55 to 80
LNK_OHSP
–40 to 245
LNK_AOZT
65 to 90
LNK_UCSP
40 to 80
LNK_UHSP
–40 to 245
LNK_AZT
0 to 65535
BKPREPTM
0 to 4194303
DEVIAQ
0 to 4194303
DEVOAQ
0 to 4194303
DEVOARH
0 to 4194303
DEVOAT
0 to 4194303
DEVRARH
0 to 4194303
DEVRAT
0 to 4194303
DEVSPRH
0 to 4194303
DEVSPT
0 to 127
BAC_MAC
0 to 4194302
BAC_ID
DEFAULT