Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 150

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
TABLE NAME
DISPLAY NAME
Med Cooling IDF Speed
High Cooling IDF Speed
Shut Down on IDF Failure
VFD Hand Mode Shutdown?
IDF VFD Motor In Reverse
IDF Danfoss Min Ref
IDF Danfoss Max Ref
IDF Danfoss Comm. TO
IDF Danfoss Auto Reset
IDF Danfoss RFI Filter
IDF ABB motor direction
IDF ABB Switching Freq.
IDF ABB Relay Cfg.
IDF ABB Ext. Relay Cfg.
IDF ABB EXT 1 Commands
IDF ABB EXT 1 Ref Select
IDF ABB ConstSpeed 7
IDF ABB Run Enable
IDF ABB Start Enable 1
IDF_CFG
IDF ABB Fault Reset Sel
(cont)
IDF ABB Start Function
IDF ABB Stop Function
IDF ABB Stall Function
IDF ABB Stall Time
IDF VFD Motor Volts
IDF VFD Motor HP
IDF VFD Motor Freq.
IDF VFD Motor Current
IDF VFD Max Current
IDF VFD Motor Nom. RPM
IDF VFD Accel. Time
IDF VFD Decel. Time
Low Cool Compressor
1 = Compressor A1
2 = Compressor A2
COOL_CFG
Compressor Min On Time
Compressor Min Off Time
Runtime to Reset Strikes
Cool Stage Increase Time
Table U — SERVICE CONFIGURATION TABLES (cont)
RANGE
20 to 100
20 to 100
Yes/No
Yes/No
Yes/No
0 to 65
0 to 65
1 to 600
0 to 600
On/Off
x
x
x
x
x
x
x
x
x
x
x
x
x
x
50 to 1000
1 to 26
20 to 400
0.1 to 40
0 to 655.35
100 to 60000
1 to 1800
1 to 1800
1 to 2
180 to 600
120 to 600
120 to 999
120 to 999
UNITS
POINT NAME
%
FSPD_MCL
%
FSPD_HCL
FATALFAN
HANDSHUT
VFD1MDIR
Hz
MINREF
Hz
MAXREF
sec
CNT_TOUT
sec
ARSTRT_T
RFIFILTR
VFDABBMD
VFD1SWFQ
ABBRELAY
ABBEXRLY
ABB_EXT1
ABB_EXTS
Hz
ABB_CSP7
VFDRUNEN
VFDSTAEN
VFDFLTRE
VFDSTAFN
VFDSTPFN
VFDSTLFN
sec
VFDSTLTM
volts
MOTVOLT
horsepower
MOTPWRHP
Hz
MOTFREQ
Amps
MOTCUR
Amps
VFD1MAXA
rpm
MOTNOMSP
sec
RAMPUP_T
sec
RAMPDN_T
LC_COMP
sec
C_MINON
sec
C_MINOFF
sec
MIN_ON_S
sec
CSTAGINC
150
DEFAULT
67 (sizes 07-12)
79 (sizes 14)
82 (sizes 17)
62 (sizes 20)
65 (sizes 24)
72 (sizes 26)
87 (sizes 04)
71 (sizes 05)
69 (sizes 06)
100
Yes
Yes
No (sizes 04-12)
Yes (sizes 14-26)
0
60
30
30
On
2
2
8
0
2
2
0
7
4
7
0
1
2
10
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
60
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
See VFD Motor Default
Configuration Tables.
Table 35 (sizes 04-06)
Table 42 (Vert. sizes 07-26)
Table 43 (Horz. Sizes 14-26)
10
10
1
300
180
300
450

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lc series

Table of Contents