Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 149

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
TABLE NAME
DISPLAY NAME
Humidistat Switch Type
Filter Status Switch Type
Remote Occupancy Sw Type
Remote Shutdown Sw Type
COFS Switch Type
General Status Sw Type
Enthalpy Switch Type
IAQ Override Switch Type
General Status shutdown?
INPUTCFG
(cont)
Remote Shutdown ALM Type
Fire Shutdown Switch
SPRH Sensor Value at 4mA
SPRH Sensor Value at 20mA
IAQ Sensor Value at 4mA
IAQ Sensor Value at 20mA
OAQ Sensor Value at 4mA
OAQ Sensor Value at 20mA
OARH Sensor Value at 4mA
OARH Sensor Val. at 20mA
RARH Sensor Value at 4mA
RARH Sensor Value at 20mA
OACFM value at 4MA
OACFM Value at 20mA
Indoor Fan Type
Number Of Fan Speeds
Fan On When Occupied
IDF Maximum Fan Speed
Ventilation Only IDF Spd
IDF_CFG
Heating IDF Speed
Free Cooling IDF Speed
Low Cooling IDF Speed
Table U — SERVICE CONFIGURATION TABLES (cont)
RANGE
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0 = Normally Open,
1 = Normally Closed
0=NORM OPEN,
1=NORM CLSD
Yes/No
0=Normal,
1=Emergency
0 =Normally Open,
1 =Normally Closed,
2 =No Switch
0 to 100
0 to 100
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
0=None,
1=VFD,
2=DIRECT DRIVE
2 to 3
Yes/No
80 to 100
0 to 100
20 to 100
0 to 100
20 to 100
UNITS
POINT NAME
HUMD_CFG
FILT_CFG
RMOC_CFG
ROFF_CFG
COFS_CFG
GENS_CFG
ENTH_CFG
IAQOSCFG
GENFATAL
ROFFTYPE
FIRE_CFG
%
SPRH_4MA
%
SPRH20MA
ppm
IAQ_4MA
ppm
IAQ_20MA
ppm
OAQ_4MA
ppm
OAQ_20MA
%
OARH_4MA
%
OARH20MA
%
RARH_4MA
%
RARH20MA
cfm
OCFM_4MA
cfm
OCFM20MA
IDFTYPE
NUMFSPDS
FANON_OC
%
SPEEDMAX
%
FSPDVENT
%
FSPD_HT
%
FSPD_FCL
%
FSPD_LCL
149
DEFAULT
0=NORM OPEN
0=NORM OPEN
0=NORM OPEN
1=NORM CLSD
0=NORM OPEN
0=NORM OPEN
0=NORM OPEN
Yes
0=Normal
2: no FIOP
0: FIOP
0
2000
0
2000
0
100
0
100
1=VFD: all except Direct Drive
motor Option
2 = DIRECT DRIVE: on 04-06
size with direct drive motors
2
Yes
100
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
50 (sizes 04-06)
100
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
70 (size 04)
57 (sizes 05-06)
67 (sizes 07-12)
53 (sizes 14 or 20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
70 (size 04)
57 (sizes 05-06)