POINT DESCRIPTION
Active Occupancy control
Alert from thermostat
Analog Input IAQ Control
Backup and Restore
BACnet BMS baud rate
BAS Protocol Select
BMS Occupancy Request
Communications status
Comp. Framework
Cool demand Limit Level
Fan Based Dehum Type
Filter Status Sw Channel
Filter Status Swith Type
Firmware Release State
Heat demand Limit Level
IAQ override sw channel
IDF VFD Fault Detail
IDF VFD Nom Motor HP Num
IDF VFD RFI Filter
IDF VFD Switch Frequency
IDF VFD Warning Detail
Indoor Fan Type Cfg
Keep configuration
Linkage Occupied Request
Operation Status Color
Remote Occupancy Channel
Remote Occupancy Sw Type
Running Mode Operation
System Demand
System Mode
Test Inactivity Time Out
Thermostat Hardware Type
Type of Heat Installed
Unit Control Type
Ventilation Status
When to Unocc Free Cool?
* BACnet is a registered trademark of ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers).
APPENDIX E — BACNET POINTS LIST
Table AA — BACnet* MSV Points List
POINT ACCESS
UNITS
READ ONLY
READ ONLY
R/W
READ ONLY
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
READ ONLY
R/W
R/W
READ ONLY
READ ONLY
R/W
R/W
READ ONLY
R/W
R/W
R/W
READ ONLY
R/W
R/W
READ ONLY
READ ONLY
READ ONLY
R/W
R/W
R/W
R/W
READ ONLY
R/W
BACNET
BACNET
OBJECT NAME
occ_ctrl
MSV:14
tstat_alert
MSV:8
iaqancfg
MSV:25
bac_rest
MSV:44
bac_baud
MSV:18
bms_cfg
MSV:11
bms_occ
MSV:12
e0commst
MSV:17
sysvtype
MSV:2003 0 to 2
cdlm_level
MSV:56
fbd_type
MSV:58
filter_channel
MSV:41
filt_cfg
MSV:42
fw_state
MSV:19
hdlm_level
MSV:57
iaqo_sw_chan
MSV:444
svfdflt
MSV:23
motpwr
MSV:22
rfi_filter
MSV:4
switch_freq
MSV:7
vfd_warning
MSV:3001 0 to 5
idftype
MSV:450
keepconf
MSV:47
lnk_occ
MSV:13
color
MSV:9
rmocchan
MSV:46
rmoc_cfg
MSV:45
sub_mode
MSV:43
sys_demand_enum
MSV:101
sys_mode
MSV:2002 0 to 2
test_ito
MSV:156
tstat_type
MSV:5
ht_type
MSV:16
control_type
MSV:2
ventstat
MSV:6
ufc_cfg
MSV:24
172
VALUE
CCN POINT
ID
RANGE
EQUIVALENT
0 to 6
OCC_CTRL
0 to 65535
THM_ALT
0 to 3
IAQANCFG
0 to 2
0 to 5
BAC_BAUD
0 to 2
BMS_CFG
0 to 2
BMS_OCC
0 to 1
E0COMMST
SYSVTYPE
0 to 3
CDMDLLEV
0 to 2
FBD_TYPE
0 to 5
FILTCHAN
0 to 2
FILT_CFG
0 to 2
FW_STATE
0 to 3
HDMDLLEV
0 to 5
IAQOCHAN
0 to 17
SVFDFLT
0 to 500
MOTPWR
0 to 1
RFIFILTR
0 to 10
SWTFREQ
SVFDWAR
0 to 2
IDFTYPE
0 to 2
KEEPCONF
0 to 2
LNK_OCC
0 to 15
COLOR
0 to 5
RMOCCHAN
0 to 1
RMOC_CFG
0 to 2
SUB_MODE
0 to 255
SYS_DMDE
SYSMODE
0 to 2
TEST_ITO
0 to 3
STATTYPE
0 to 2
HEATTYPE
0 to 2
CTRLTYPE
0 to 9
VENTSTAT
0 to 2
UFC_CFG