Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 174

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

MODEL NO._______________________________________
SERIAL NO._______________________________________
DATE_____________________________________________
TECHNICIAN______________________________________
CONTROL TYPE:
SETPOINT
DISPLAY TEXT
SETTINGS
SPACE SET POINTS
OCC COOL SETPOINT
OCC HEAT SETPOINT
UNOCC COOL SETPNT
UNOCC HEAT SETPNT
HEAT-COOL SP GAP
SPT SLIDER RANGE
OCC SPRH SET PT
UNOCC SPRH SET PT
SA TEMPER SET PNT
TEMP DEMAND CONFIG
LOW COOL DMD ON
MED COOL DMD ON
HIGH COOL DMD ON
LOW COOL DMD OFF
COOL DMD LEVEL UP
LOW HEAT DMD ON
HIGH HEAT DMD ON
LOW HEAT DMD OFF
HEAT DMD LEVEL UP
DEMAND TIMEGUARD1
DEMAND TIMEGUARD2
DEMAND TIMEGUARD3
DMD LIMIT CONFIG
COOL DMD LIM LEV1
COOL DMD LIM LEV2
COOL DMD LIM LEV3
HEAT DMD LIM LEV1
HEAT DMD LIM LEV2
HEAT DMD LIM LEV3
CLOCK
TIME
DATE
DAYLIGHT SAVINGS
DAYLIGHT SAVINGS?
CONTROL SET POINT AND CONFIGURATION LOG
INDICATE UNIT SETTINGS BELOW
Thermostat/T55 Space Temp./T-56 Space Temp./T-59 Space Temp.
Cooling
Occupied:_________________
Heating
Occupied:_________________
Table AC — Settings Main Menu Layout
EXPANDED TEXT
Settings Menu
Space Setpoints Adjustment
Menu
Occupied Cool Setpoint
Occupied Heat Setpoint
Unoccupied Cool Setpoint
Unoccupied Heat Setpoint
Heat-Cool Setpoint Gap
SPT Offset Range (±)
Occupied SPRH Setpoint
Unoccupied SPRH Setpoint
SA Tempering Setpoint
Temperature Demand
Configuration Menu
Low Cool Demand On
Medium Cool Demand On
High Cool Demand On
Low Cool Demand Off
Cool Demand Level Up
Low Heat Demand On
High Heat Demand On
Low Heat Demand Off
Heat Demand Level Up
Space Demand Time Guard1 60 to 600
Space Demand Time Guard2 0 to 600
Space Demand Time Guard3 5 to 120
DEMAND LIMIT CONFIG
Cool DMD Offset level 1
Cool DMD Offset level 2
Cool DMD Offset level 3
Heat DMD Offset level 1
Heat DMD Offset level 2
Heat DMD Offset level 3
Clock Adjustment Menu
Clock Hour and Minute
Current Date
Daylight Savings
Configuration Menu
DST allowed?
SOFTWARE VERSIONS:
MBB:CESR131651–_________________________________
VFD FW VERSION–________________________________
Unoccupied:_______________
Unoccupied:_______________
RANGE
UNITS
55 to 80
°F
78
55 to 80
°F
68
65 to 95
°F
85
40 to 80
°F
60
2 to 10
^F
5
0 to 5.0
°F
5
0 to 100
%
55
0 to 100
%
55
xx
°F
50
–1 to 2.0
°F
0.5
0.5 to 20.0
°F
1
0.5 to 20.0
°F
2
–1 to 2.0
°F
–0.5
–2 to 2.0
^F/min
–0.2
–1 to 2.0
°F
0.5
0.5 to 20.0
°F
2
–1 to 2.0
°F
–0.5
–2 to 2.0
^F/min
–0.2
sec
180
sec
300
min
10
0 to 99
°F
1
0 to 99
°F
3
0 to 99
°F
5
0 to 99
°F
1
0 to 99
°F
3
0 to 99
°F
5
xx:xx
hh.mm
MM/DD/YYYY
Enable/Disable
Enable
174
DEFAULT
POINT
OCSP
OHSP
UCSP
UHSP
HCSP_GAP
SPTO_RNG
SPRH_OSP
SPRH_USP
SATEMPSP
DMDLCON
DMDMCON
DMDHCON
DMDLCOFF
CDMD_LUP
DMDLHON
DMDHHON
DMDLHOFF
HDMD_LUP
TDMD_TG1
TDMD_TG2
TDMD_TG3
CLDOLEV1
CLDOLEV2
CLDOLEV3
HTDOLEV1
HTDOLEV2
HTDOLEV3
TIME
DATE
DST Menu