Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 154

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
TABLE NAME
DISPLAY NAME
PE1 Relay Channel
PE Turn Off Deadband
PE2 Relay Channel
PE Stage 2 at Max Speed
ECON_CFG
(cont)
T24 Heat/Cool End Delay
T24Econ Min Move for SAT
Damper SAT Deadband
T24 Min Diff in RAT-OAT
T24 Test Minimum Pos
T24 Test Maximum Pos
Analog Input IAQ Control
0 =No IAQ
1 =DCV
2 = IAQ Override
3 =MINPOS Control
IAQ Position at Max Fan
AQ Differential Low
AQ Differential High
IAQ Preoccupancy Purge
IAQ_CFG
IAQ Purge Pos at Max IDF
Preocc Purge Lockout OAT
Preocc Purge Duration
IAQ Sensor Value at 4mA
IAQ Sensor Value at 20mA
OAQ Sensor Value at 4mA
OAQ Sensor Value at 20mA
IAQ Override Sw Channel
IAQ Override Switch Type
ALM Relay Assigned Chan
0 =None
1 =MBB RLY11
2 =MBB RLY06
Thermostat Alerts
Hardware Failures Alerts
SAT/RAT Sensor Alerts
OAT Thermistor Alerts
Space Sensors Alerts
Transducer Sensor Alerts
RH Sensor Failure Alert
ALM_CFG
Air Quality CO
2
OACFM Alarm Relay
Economizer Alerts
Dirty Filter Alerts
General Status Alerts
Refrig Circuit Alerts
Compressor Alerts
Heating Failure Alerts
Indoor Fan Alerts
Relay on Active IOBA
Relay on Active Faults
Zone Sensor 1 Address
Zone Sensor 2 Address
ZSENSCFG
Zone Sensor 3 Address
Zone Sensor 4 Address
Zone Sensor 5 Address
Table U — SERVICE CONFIGURATION TABLES (cont)
RANGE
0=NONE,
1=MBB RLY11,
2=MBB RLY06
0 to 100
0=NONE,
1=MBB RLY11,
2=MBB RLY06
0 to 100
0 to 60
10 to 20
0 to 20
5 to 20
0 to 100
0 to 100
0 to 3
0 to 100
0 to 5000
0 to 5000
Yes/No
0 to 100
0 to 70
5 to 120
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 6
Yes/No
0 to 2
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Alerts
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
UNITS
POINT NAME
PE1_CHAN
%
PE_OFFDB
PE2_CHAN
%
PE2_PMAX
min
T24CHDLY
%
T24ECSTS
°F
T24SATDB
°F
T24RATDF
%
T24TSTMN
%
T24TSTMX
IAQANCFG
%
IAQMINP
ppm
DAQ_LOW
ppm
DAQ_HIGH
IAQPURGE
%
IAQPMAX
°F
IAQP_LA
min
IAQPTIME
ppm
IAQ_4MA
ppm
IAQ_20MA
ppm
OAQ_4MA
ppm
OAQ_20MA
IAQOCHAN
IAQOSCFG
ALM_CHAN
TSTAT_AL
HW_AL
SATRATAL
OATRL_AL
SPACE_AL
TRANS_AL
RHS_AL
CO2S_AL
OACFM_AL
ECON_AL
FILT_AL
GENS_AL
CKT_AL
COMP_AL
HEAT_AL
FAN_AL
IOBFA_AL
FAULT_AL
ZSADDR1
ZSADDR2
ZSADDR3
ZSADDR4
ZSADDR5
154
DEFAULT
0: no FIOP
2: FIOP
5
0=None
75
25
10
12
15
15
85
0: no FIOP
1: FIOP
10
100
700
Yes
40
50
15
0
2000
0
2000
1=MBB RLY11
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
255
255
255
255
255