APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY
DISPLAY TEXT
INDOOR FAN (cont)
VFD WARN DETAIL
IDF VFD Warning Detail
GENERAL
General Run Data Menu
FILTER TIME LEFT
Filter hour remaining
RESET FILTER TIME
Reset Filter Timer
IN DAYLIGHT SAVE?
DST currently active
TCS ACTIVE?
Temp Compensate Start On
OCCUPANCY
OCCUPANCY DATA
OCCUPIED NOW
Currently Occupied
MINS UNTIL OCC
Mins until next occupied
ACTIVE OCC CTRL
Active Occupancy control
LINKAGE OCC REQ
Linkage Occupied Request
TIMED OVRD REMAIN
Timed Override Remaining
REMOTE OCC SWITCH Remote Occupancy Switch
BMS OCC REQUEST
BMS Occupancy Request
LOCAL OCC REQUEST
Local Sched Occ Request
ACTIVE PERIOD
Active Schedule period
HOLIDAY TOMORROW? Tomorrow Is A Holiday
HOLIDAY TODAY?
Today Is A Holiday
NEXT OCC DAY
Next Occupied Day
NEXT OCC TIME
Next Occupied Time
NEXT UNOCC DAY
Next Unoccupied Day
NEXT UNOCC TIME
Next Unoccupied Time
PREV UNOCC DAY
Previous Unoccupied Day
PREV UNOCC TIME
Previous Unoccupied Time
Table A — Run Status Main Menu Layout (cont)
EXPANDED TEXT
91
VALUES
UNITS WRITE STATUS
0=NONE,
1=VOLTAGE,
2=CURRENT,
3=THERMAL,
4=MULTIPLE,
5=UNEXPECT
xxxx
hours
Yes/No
n/a
Command
Yes/No
n/a
Yes/No
n/a
Yes/No
Forcible
xxxxx
min
0=24/7 OCC,
1=SCHEDULE,
2=BAS CTRL,
3=REMOC CTL,
4=TIME OVRD,
5=LINKAGE,
6=FORCED
0=Unocc,
1=Occupied,
2=Disabled
0 to 240
min
Forcible
On/Off
Forcible
0=UNOCC,
1=OCCUPIED,
Forcible
2=DISABLED
0=Unocc,
Forcible
1=Occupied
0 to 8
Yes/No
Yes/No
DDD
hh:mm
DDD
hh:mm
DDD
hh:mm
POINT
SVFDWAR
FILTLEFT
RESETFLT
DST_ACTV
TCS_ACT
OCCUPIED
MINTILOC
OCC_CTRL
LNK_OCC
OVR_EXT
REMOCC
BMS_OCC
LOC_OCC
PER_NO
HOL_TMRW
HOLTODAY
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM