APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
TABLE
DISPLAY NAME
Linkage Start Bias Time
LINKDATA
(cont)
Value of Prime Variable
Currently Occupied
Active Occupancy Control
Linkage Occupied Request
Timed Override Remaining
Remote Occupancy Switch
BMS Occupancy Request
Local Sched Occ Request
Active Schedule Period
Mins until next occupied
BACnet Cal Object Status
Today Is A Holiday
Tomorrow Is A Holiday
Next Occupied Day
OCC_DIAG
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Previous Unccupied Day
Previous Unoccupied Time
Accept Global Holidays?
Global Schedule Broadcast
CCN Schedule Number
0 = Always Occupied
1-64 = Local Schedule
65-99 = Global Schedule
Remote Occupancy Channel
Remote Occupancy Switch
Timed Override Duration
BAS Protocol Select
Assigned AI06 Function
HW_IO
Assigned AI07 Function
Assigned AI08 Function
Table T — MAINTENANCE TABLES (cont)
xxx
xxx.x
Yes/No
0 = 24/7 OCC,
1 = Schedule,
2 = BASCTRL,
3 = REMOC CTL,
4 = Time Override,
5 = Linkage,
6 = Forced
0=Unocc,
1=Occupied,
2=Disabled
0 to 240
On/Off
0=Unocc,
1=Occupied,
2=Disabled
0=Unocc,
1=Occupied
0 to 8
–1 to 10080
Yes/No
Yes/No
Yes/No
DDD
hh:mm
DDD
hh:mm
DDD
hh:mm
Yes/No
Yes/No
0 to 99
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
On/Off
0 to 4
0=NONE,
1=CCN,
2=BACNET
0 =None,
1 = IAQ,
2 =OARH,
3 = RARH,
4 =OAQ,
5 = SPRH,
6 =OACFM
0 =None,
1 = IAQ,
2 =OARH,
3 = RARH,
4 =OAQ,
5 = SPRH,
6 =OACFM
0 =None,
1 = IAQ,
2 =OARH,
3 = RARH,
4 =OAQ,
5 = SPRH,
6 =OACFM
143
RANGE
UNITS
min
°F
min
min
hh.mm
hours
WRITE
POINT NAME
STATUS
LNK_SBT
Forcible
PRIME_V
OCCUPIED
Forcible
OCC_CTRL
LNK_OCC
Forcible
OVR_EXT
Forcible
REMOCC
Forcible
BMS_OCC
Forcible
LOC_OCC
Forcible
PER_NO
MINTILOC
CALOBJST
HOLTODAY
HOL_TMRW
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
PRVUNDAY
PRVUNTIM
HOLIDAYT
CCN_GSBC
SCHEDNUM
RMOCCHAN
REMOCC
Forcible
OTL_CFG
BMS_CFG
MBBAI06F
MBBAI07F
MBBAI08F

Hide quick links: