Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 179

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

CONTROL SET POINT AND CONFIGURATION LOG
DISPLAY TEXT
ODF SETTINGS
ODF SIGNAL QTY
ODF LOW COOL SPD
ODF MED COOL SPD
ODF HIGH COOL SPD
ODF MAXIMUM SPEED
ODF MINIMUM SPEED
HEATING
UNIT TYPE OF HEAT
HEATING STAGE QTY
HEAT MIN ON
HEAT MIN OFF
HEAT STAGEUP TIME
HEAT SATTREND LEV
LOWER MAX SAT
UPPER MAX SAT
HEAT FANOFF DELAY
HEAT LOCKOUT OAT
SAT DURING HEAT?
IGC IFO TIMEOUT
PREHEAT W/O IDF?
PREHEAT FAN DELAY
SA TEMPER ENABLED
Table AC — Settings Main Menu Layout (cont)
EXPANDED TEXT
Outdoor Fans Configurations
Menu
Number of ODF Outputs
ODF Low Cool Speed
ODF Med Cool Speed
ODF High Cool Speed
ODF Maximum Speed
ODF Minimum Speed
Heating Configurations Menu
Type of Heat Installed
Number of Heating Stages
Heat Minimum On Time
Heat Minimum Off Time
Heat Stage Increase Time
Heating SAT Trend Level
Heat Max SAT Lower Level
Heat Max SAT Upper Level
Heating Fan-off Delay
Heating Lockout Temp
SAT Heat Mode Sensing
No IGC IFO input Timeout
Pre-Heat HX without IDF?
Pre-Heat Fan On Delay
Supply Air Tempering Enable Yes/No
RANGE
UNITS
1 (sizes 04-06)
2 (sizes 07,17,
0 to 3
or 20)
3 (sizes 08-14,
24-26)
1000 (size 04)
1075 (sizes 05-
06)
550 (sizes 07-
0 to 1200
rpm
12)
700 (sizes 14-
17, 26)
650 (sizes 20-
24)
1000 (size 04)
1075 (sizes 05-
06)
700 (sizes 07,
12, or 24)
0 to 1200
rpm
600 (size 08)
650 (size 09)
800 (sizes
14,17, or 26)
750 (size 20)
1000 (size 04)
1075 (sizes 05-
06)
950 (sizes 07 or
0 to 1200
rpm
09)
900 (size 08)
1000 (sizes 12-
26)
1000 (size 04)
1075 (sizes 05-
06)
950 (sizes 07 or
0 to 1200
rpm
09)
900 (size 08)
1000 (sizes 12-
26)
0 to 1200
rpm
160
0=ELECTRIC,
0 (50 series)
1=GAS
1 (48 series)
2 (all except
below);
0 (50 series
without
FIOP heat),
1 (50 Series,
sizes 04-06 low
or medium
0 to 2
heat),
1 (50 series,
sizes
07-14 and low
heat),
1 (50 series,
sizes 07-12 and
medium heat)
60 to 600
sec
120
60 to 600
sec
120
120 to 999
sec
450
-1 to 1.0
^F/min
0.2
85.0 to 200.0
°F
140
85.0 to 200.0
°F
160
30 (50 series)
10 to 600
sec
45 (48 series)
40 to 125
°F
75
Enable/Disable
Enable
0 to 60
min
5
Enable/Disable
Disable
0 to 120
sec
30
Yes
179
DEFAULT
POINT
NUM_ODF
ODFLCSPD
ODFMCSPD
ODFHCSPD
ODFMAXSP
ODFMINSP
HEATTYPE
NUMHSTGS
H_MINON
H_MINOFF
HSTAGINC
SAT_TLH
SATMAX_L
SATMAX_H
HEAT_FOD
OATLHEAT
SAT_HEAT
NO_IGCTM
PREHT_HX
PREHT_TM
SATEMPEN
ENTRY

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lc series

Table of Contents