POINT DESCRIPTION
Ok to fan based dehum
Ok to Dehumidify?
Ok to Preoccupancy Purge
OK to Run Heat
OK to SupplyAirTempering
Ok to Unocc Free Cool?
Ok to use compressors?
OK to Use Free Cooling?
Ok to use humidimizer
Percent Enable/Disable
Power Exhaust 1 Relay
Power Exhaust 1 Test
Power Exhaust 2 Relay
Power Exhaust 2 Test
RARH Open Circuit Alert
RARH Sensor Error
RARH Short Circuit Alert
RAT Open Circuit Alert
RAT out of Range Alert
RAT out of Range Alert
RAT Sensor Error
RAT Short Circuit Alert
Refrig Circuit Alerts
Reheat Dischg Valve CirA
Reheat Liq Valv Rly Test
Reheat Liquid Valve CirA
Remote Occupancy Switch
Remote shutdown fault
Remote Shutdown Switch
Reset All Current Alarms
Reset Filter Timer
RH sensor failure Alert
Rht Dischg Valve Rly Tst
Rollout without Heating
RUN AUTO COOLING TEST
RUN AUTO HEATING TEST
RUN AUTO SYSTEM TEST
Run away heat fault
SAT Sensor Error
SAT/RAT Sensor Alerts
SDPA Sensor Error
Shut Down on IDF Failure
Shutdown A1 First
Shutdown A2 First
Shutdown Loader First
Smoke Purge Input
Space Sensors Alerts
SPRH Open Circuit Alert
SPRH Short Circuit Alert
SPT Open Circuit Alert
SPT Sensor Error
SPT Short Circuit Alert
SPTO Sensor Error
SPToutofRangeAlert
SSPA Sensor Error
Start Config Restore
Supply Air Temper Enable
System Demand Alarm
Temp Compensate Start On
Thermostat Alerts
Thermostat G Input
APPENDIX E — BACNET POINTS LIST
Table Z — BACnet* BV Points List (cont)
POINT ACCESS
UNITS
READ ONLY
READ ONLY
READ ONLY
READ ONLY
READ ONLY
READ ONLY
READ ONLY
READ ONLY
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
READ ONLY
R/W
R/W
READ ONLY
R/W
R/W
BACNET
BACNET
OBJECT NAME
oktofbd
BV:420
oktodhum
BV:422
okpreocc
BV:35
oktoheat
BV:36
oktotemp
BV:415
oktoufc
BV:37
okmechcl
BV:302
ok_free_cl
BV:65
oktohumz
BV:421
perc_bac
BV:303
pe1
BV:15
s_pe_1
BV:82
pe2
BV:66
s_pe_2
BV:83
a_opnrrh
BV:199
rarh_err
BV:67
a_shtrrh
BV:210
a_opnrat
BV:198
a_badrat
BV:187
a_badsat
BV:188
rat_err
BV:68
a_shtrat
BV:209
circuit_alarm
BV:313
rdv_a
BV:7012
s_rlv_a
BV:455
rlv_a
BV:7051
remocc
BV:29
f_remoff
BV:272
rem_shut
BV:9001
alarm_reset
BV:33
reset_filter_timer
BV:109
rhs_al
BV:308
s_rdv_a
BV:282
f_ronoht
BV:235
autocool
BV:160
autoheat
BV:161
autosys
BV:162
f_hstuck
BV:266
sat_err
BV:84
sa_ra_alarm
BV:311
sdpa_err
BV:63
sfan_fail_alarm
BV:7008
sdwn_a1
BV:449
sdwn_a2
BV:450
sdwn_ald
BV:451
purge
BV:80
space_alarm
BV:103
a_opnsrh
BV:274
a_shtsrh
BV:275
a_opnspt
BV:201
space_err
BV:7001
a_shtspt
BV:212
stpt_err
BV:7002
a_badspt
BV:190
sspa_err
BV:89
ddrstre
BV:130
sup_air_temp_en
BV:410
sys_dmd_alarm
BV:26
tcs_Act
BV:133
tstat_al
BV:104
g_input
BV:1021
170
VALUE
CCN POINT
ID
RANGE
EQUIVALENT
0 to 1
OKTOFBD
0 to 1
OKTODHUM
0 to 1
OKPREOCC
0 to 1
OKTOHEAT
0 to 1
OKTOTEMP
0 to 1
OKTOUFC
0 to 1
OKMECHCL
0 to 1
OKFREECL
0 to 1
OKTOHUMZ
0 to 1
PERC_BAC
0 to 1
PE1
0 to 1
S_PE_1
0 to 1
PE2
0 to 1
S_PE_2
0 to 1
0 to 1
RARH_ERR
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
RAT_ERR
0 to 1
0 to 1
CKT_AL
0 to 1
RDV_A
0 to 1
S_RLV_A
0 to 1
RLV_A
0 to 1
REMOCC
0 to 1
0 to 1
REMSHUT
0 to 1
ALRESET
0 to 1
RESETFLT
0 to 1
RHS_AL
0 to 1
S_RDV_A
0 to 1
0 to 1
AUTOCOOL
0 to 1
AUTOHEAT
0 to 1
AUTOSYS
0 to 1
0 to 1
SAT_ERR
0 to 1
SATRATAL
0 to 1
SDPA_ERR
0 to 1
FATALFAN
0 to 1
SDWN_A1
0 to 1
SDWN_A2
0 to 1
SDWN_ALD
0 to 1
PURGE
0 to 1
SPACE_AL
0 to 1
0 to 1
0 to 1
0 to 1
SPT_ERR
0 to 1
0 to 1
SPTO_ERR
0 to 1
0 to 1
SSPA_ERR
0 to 1
DDRSTRE
0 to 1
SATEMPEN
0 to 1
SYSDMDAL
0 to 1
TCS_ACT
0 to 1
TSTAT_AL
0 to 1
G

Hide quick links: