Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 180

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

CONTROL SET POINT AND CONFIGURATION LOG
DISPLAY TEXT
HEATING (cont)
SA TEMPER SET PNT
TEMPER MAX OUT
INDOOR FAN
INDOOR FAN TYPE
DIR.DRV IDF SPDS
OCCUPIED FAN?
MAXIMUM IDF SPEED
VENT IDF SPEED
HEATING IDF SPD
FREE COOL IDF SPD
LOW COOL IDF SPD
MED COOL IDF SPD
HIGH COOL IDF SPD
SHUTDOWN IDF FAIL
SHUTDOWN VFD HAND
VFD IN REVERSE?
IDF VFD PARAMETERS
IDF VFD NOM. HP
Table AC — Settings Main Menu Layout (cont)
EXPANDED TEXT
SA tempering Setpoint
Max OAT for SA tempering
Indoor Fan Configurations
Menu
Indoor Fan Type
Number Of Fan Speeds
Fan On When Occupied
IDF Maximum Fan Speed
Ventilation Only IDF Spd
Heating IDF Speed
Free Cooling IDF Speed
Low Cooling IDF Speed
Med Cooling IDF Speed
High Cooling IDF Speed
Shut Down on IDF Failure
VFD Hand Mode Shutdown?
IDF VFD Motor In Reverse
Indoor Fan VFD Settings
Menu
IDF VFD Motor HP
RANGE
UNITS
xx
°F
50
-40 to 125
°F
48
1=VFD: all
except Direct
Drive motor
0=None,
Option
1=VFD,
2 = DIRECT
2=DIRECT DRIVE
DRIVE: on 04-
06 size with
direct drive
motors
2 to 3
2
Yes/No
Yes
80 to 100
%
100
50 (sizes 04-06)
67 (sizes 07-12)
53 (sizes 14 or
0 to 100
%
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
20-100
%
100
70 (size 04)
57 (sizes 05-06)
67 (sizes 07-12)
53 (sizes 14 or
0-100
%
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
70 (size 04)
57 (sizes 05-06)
67 (sizes 07-12)
53 (sizes 14 or
20-100
%
20)
56 (sizes 17)
52 (sizes 24)
60 (sizes 26)
87 (sizes 04)
71 (sizes 05)
69 (sizes 06)
67 (sizes 07-12)
20-100
%
79 (sizes 14)
82 (sizes 17)
62 (sizes 20)
65 (sizes 24)
72 (sizes 26)
20-100
%
100
Yes/No
Yes
Yes/No
Yes
No (sizes 04-12)
Yes/No
Yes (sizes 14-
26)
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
1 to 26
HP
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
180
DEFAULT
POINT
SATEMPSP
OATSTEMP
IDFTYPE
NUMFSPDS
FANON_OC
SPEEDMAX
FSPDVENT
FSPD_HT
FSPD_FCL
FSPD_LCL
FSPD_MCL
FSPD_HCL
FATALFAN
HANDSHUT
VFD1MDIR
MOTPWRH
P
ENTRY

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50lc series

Table of Contents