Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 176

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

DISPLAY TEXT
UNIT CONFIGURATIONS (cont)
TEST MODE TIMEOUT
CCH MAX TEMP
STD BARO PRESSURE
LINK STAGEUP TIME
UNIT'S MAX SAT
AUTO SAT FAULTS?
ADAPTIVE TCS?
USER TCS BIASTIME
SWITCH INPUTS CONFIGS
FIRE SHUTDOWN SW
HUMSTAT CHANNEL
HUMSTAT SW TYPE
FILTER SW CHANNEL
FILTER SW TYPE
REMOTE OCC CHAN
REMOTE OCC TYPE
REM.SHUTDOWN CHAN
REM.SHUTDOWN SW T
REM.SHUTDOWN TYPE
COFS CHANNEL
COFS TYPE
GEN STATUS CHAN
GEN STAT SW TYPE
SHUTDOWN GEN STAT
CONTROL SET POINT AND CONFIGURATION LOG
Table AC — Settings Main Menu Layout (cont)
EXPANDED TEXT
Test inactivity time out
CCH Max Temperature
Std Barometric Pressure
Linkage Stage inc. time
Unit's Maximum SAT
Auto Clr SAT Limit Fault
Adaptive Temp Comp Start
User TCS Start bias time
DI Config Menu
Fire Shutdown Switch
Humidistat Status Channel
Humidistat Switch Type
Filter Status Sw Channel
Filter Status Switch Type
Remote Occupancy Channel
Remote Occupancy Sw Type
Remote Shutdown Channel
Remote Shutdown Sw Type
Remote Shutdown ALM Type
COFS Assigned Channel
COFS Switch Type
General Status Channel
General Status Sw Type
General Status shutdown?
RANGE
UNITS
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours
4=4 hours,
5=8 hours,
6=12 hours
40 to 90
°F
65
13.00 to 35.00
in. Hg
29.92
60 to 600
sec
180
130 to 210
°F
200
Yes/No
No
Enable/Disable
Enable
0 to 180
min
0
0=NORM OPEN,
2: no FIOP
1=NORM CLSD,
0: FIOP
2=NO SWITCH
0=None,
1=MBB DI12,
0=for all except
2=MBB DI13.
Humidimizer
3=MBB DI14,
6=Humidimizer
4=MBB DI02,
Units
5=MBB DI04,
6=SIOB Di01
0=NORM OPEN,
0=NORM OPEN HUMD_CFG
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
0=None
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=NORM OPEN,
0=NORM OPEN FILT_CFG
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
0=None
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=NORM OPEN,
0=NORM OPEN RMOC_CFG
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
0=None
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=NORM OPEN,
0=NORM OPEN ROFF_CFG
1=NORM CLSD
0=Normal,
0=Normal
1=Emergency
0=None,
1=MBB DI12,
0=None (no
2=MBB DI13,
FIOP)
3=MBB DI14,
4=MBB DI02
4=MBB DI02,
(FIOP)
5=MBB DI04
0=NORM OPEN,
1=NORM CLSD COFS_CFG
1=NORM CLSD
0=None,
1=MBB DI12,
2=MBB DI13,
0=None
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=NORM OPEN,
0=NORM OPEN GENS_CFG
1=NORM CLSD
Yes/No
Yes
176
DEFAULT
POINT
TEST_ITO
CCHMAXT
STD_BARP
LSTAGINC
UMAX_SAT
SATLACLR
TCS_CFG
TCSUBIAS
FIRE_CFG
HUMDCHAN
FILTCHAN
RMOCCHA
N
ROFFCHAN
ROFFTYPE
COFSCHAN
GEN_CHAN
GENFATAL
ENTRY