APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY
DISPLAY TEXT
CLOCK (cont)
DST STOP MONTH
DST STOP WEEK
DST STOP DAY
DST MINS TO SUB
START TIME IN DAY
SCHEDULES
SCHEDULE NUMBER
OCCUPANCY SCHEDULE
HOLIDAYS
ALLOW G. HOLIDAY?
TIMED OVR LENGTH
UNIT CONFIGURATIONS
GENERAL
STARTUP DELAY
UNIT CONTROL TYPE
THERMOSTAT TYPE
ADAPTIVE TSTAT
DIRTY FILTER TIME
TEST MODE TIMEOUT
CCH MAX TEMP
STD BARO PRESSURE
LINK STAGEUP TIME
UNIT'S MAX SAT
AUTO SAT FAULTS?
ADAPTIVE TCS?
USER TCS BIASTIME
SWITCH INPUTS CONFIGS
FIRE SHUTDOWN SW
HUMSTAT CHANNEL
HUMSTAT SW TYPE
Table B — Settings Main Menu Layout (cont)
EXPANDED TEXT
DST Stop Month
DST Stop Week
DST Stop Day
DST Minutes to Subtract
Time in day to start DST
Schedules Adjustment Menu
CCN Schedule Number
OCCUPANCY SCHEDULE DATA
Holiday Adjustment Menu
Accept Global Holidays?
Timed Override Duration
Unit Configurations Menu
General Unit Configurations Menu
Unit Startup Delay
Unit Control Type
Thermostat Hardware Type
Tstat Adaptive Staging
Change Filter Timer
Test inactivity time out
CCH Max Temperature
Std Barometric Pressure
Linkage Stage inc. time
Unit's Maximum SAT
Auto Clr SAT Limit Fault
Adaptive Temp Comp Start
User TCS Start bias time
DI Config Menu
Fire Shutdown Switch
Humidistat Status Channel
Humidistat Switch Type
RANGE
UNITS
1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEBER,
12=DECEMBER
1 to 5
1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
0 to 90
min
0 to 600
min
0 = Always Occupied,
1-64 = Local
Schedule,
65-99 = Global
Schedule
Yes/No
0 to 4
hours
10 to 600
sec
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
4=DIGI 2C2H_S
Yes/No
0 to 9999
hours
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
40 to 90
°F
13.00 to 35.00
in. Hg
60 to 600
sec
130 to 210
°F
Yes/No
Enable/Disable
0 to 180
min
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB Di01
0=NORM OPEN,
1=NORM CLSD
93
DEFAULT
POINT
1=JANUARY
STOPM
1
STOPW
7=SUNDAY
STOPD
60
MINSUB
120
DST_TOD
0=Always Occupied
SCHEDNUM
No
HOLIDAYT
4
OTL_CFG
30
STARTDLY
0=TSTAT
CTRLTYPE
2=CONV 3C2H
STATTYPE
Yes
ADPTSTAT
600
FILTLIFE
4=4 hours
TEST_ITO
65
CCHMAXT
29.92
STD_BARP
180
LSTAGINC
200
UMAX_SAT
No
SATLACLR
Enable
TCS_CFG
0
TCSUBIAS
2: no FIOP
FIRE_CFG
0: FIOP
0=for all except
Humidimizer
HUMDCHAN
6=Humidimizer Units
0=NORM OPEN
HUMD_CFG