Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 121

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

ITEM
SETPOINTS
OCSP
OHSP
UCSP
UHSP
GAP
STO.R
RH.SP
SA.SP
APPENDIX C — NAVIGATOR™ DISPLAY
Table L — MODE – SETPOINTS
EXPANSION
Occupied Cool Setpoint
Occupied Heat Setpoint
Unoccupied Cool Setpoint
Unoccupied Heat Setpoint
Heat-Cool Setpoint Gap
SPT Offset Range (±)
Space RH Setpoint
SA Tempering Setpoint
RANGE
UNIT
55 to 80
°F
55 to 80
°F
65 to 95
°F
40 to 80
°F
2 to 10
^F
0 to 5
°F
0 to 100
%
xx
°F
121
DEFAULT
POINT
78
OCSP
68
OHSP
85
UCSP
60
UHSP
5
HCSP_GAP
5
SPTO_RNG
55
SPRH_SP
50
SATEMPSP

Hide quick links: