Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 161

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

POINT DESCRIPTION
Econo Actual Position
Econo Commanded Position
Economizer Damper Starts
Economizer Position Test
Economizer Travel Time
Effective Deadband
Effective Demand Temp
Effective Zone Setpoint
Enthalpy Cross Deadband
Equipment Touch RH
Equipment Touch SPT
Fan Supply Air Temp
FBDH Low Set Point
FBDH SAT Min value
FBDH SAT Set Point
FBDH SST Min value
Filter hour remaining
Free Cooling IDF Speed
Free Cooling Max OAT
Free Cooling Min Temp
Free Cooling Reset Count
Free Cooling Run Hours
Free Cooling Starts
Full Load Resets Count
Heat Demand Level Up
Heat DMD Offset level 1
Heat DMD Offset level 2
Heat DMD Offset level 3
Heat Minimum Off Time
Heat Minimum On Time
Heat Mode Select T.guard
Heat Setpoint in Effect
Heat Shed 1 demand band
Heat Shed 2 demand band
Heat Shed 3 demand band
Heat Space Demand Trend
Heat Stage 1 Reset Count
Heat Stage 1 Run Hours
Heat Stage 1 Starts
Heat Stage 1 Timeguard
Heat Stage 2 Reset Count
Heat Stage 2 Run Hours
Heat Stage 2 Starts
Heat Stage 2 Timeguard
Heat-Cool Setpoint Gap
Heating Fan-Off Delay
Heating IDF Speed
Heating Lockout Temp
Heating Space Demand
High Cool Demand On
High Cooling IDF Speed
High FreeCool SAT Setpnt
High Heat Demand On
HumidiMizer Level Test
IAQ Assigned Channel
IAQ DCV Curve - Pos 1
IAQ DCV Curve - Pos 2
IAQ DCV Curve - Pos 3
IAQ DCV Curve - Speed 1
IAQ DCV Curve - Speed 2
IAQ DCV Curve - Speed 3
APPENDIX E — BACNET POINTS LIST
Table Y — BACnet* AV Points List (cont)
POINT ACCESS
UNITS
READ ONLY
%
R/W
%
READ ONLY
R/W
%
R/W
sec
R/W
READ ONLY
°F
R/W
°F
R/W
BTU_LB
R/W
%
R/W
°F
READ ONLY
°F
R/W
°F delta
R/W
°F
READ ONLY
°F
R/W
°F
READ ONLY
hrs
R/W
%
R/W
°F
R/W
°F
READ ONLY
READ ONLY
hrs
READ ONLY
READ ONLY
R/W
°F
R/W
°F
R/W
°F
R/W
°F
R/W
sec
R/W
sec
READ ONLY
sec
READ ONLY
°F
R/W
R/W
R/W
READ ONLY
READ ONLY
READ ONLY
hrs
READ ONLY
READ ONLY
sec
READ ONLY
READ ONLY
hrs
READ ONLY
READ ONLY
sec
R/W
°F
R/W
sec
R/W
%
R/W
°F
READ ONLY
°F delta
R/W
°F
R/W
%
R/W
°F
R/W
°F
R/W
R/W
READ ONLY
%
READ ONLY
%
READ ONLY
%
READ ONLY
%
READ ONLY
%
READ ONLY
%
BACNET
BACNET
OBJECT NAME
dampact
AV:211
dmpr_cmd
AV:4
st_damp
AV:139
s_damper
AV:118
eceonotrv
AV:226
effdb
AV:6007
temp_eff
AV:163
effsp
AV:6006
oa_ra_diff_enth
AV:77
EquipmentTouchRH
AV:1904
EquipmentTouchSPT
AV:1902
idf_sa_temp
AV:10
fbdlosp
AV:438
fbdh_sat
AV:436
fbdsatsp
AV:441
fbdh_sst
AV:437
filter_rntm
AV:2015
fspd_free_cool
AV:230
max_free_cl_temp
AV:67
min_free_cl_temp
AV:71
rs_freec
AV:104
hour_free_cl
AV:53
st_freec
AV:141
rs_fload
AV:103
hadmd_lup
AV:239
hdlm_level1
AV:403
hdlm_level2
AV:404
hdlm_level3
AV:405
h_minoff
AV:235
h_minon
AV:236
ht_sel_timeguard
AV:45
hsp_eff
AV:243
heatsh1
AV:6011
heatsh2
AV:6012
heatsh3
AV:6013
htdtrend
AV:244
rs_htr_1
AV:106
hour_ht_1
AV:54
st_htr_1
AV:142
timgd_h1
AV:173
rs_htr_2
AV:107
hour_ht_2
AV:55
st_htr_2
AV:143
timgd_h2
AV:50
hcsp_gap
AV:238
heat_fod
AV:241
fspd_heat
AV:232
oatlheat
AV:8033
heat_dmd
AV:240
dmdhcon
AV:215
fspd_high_cool
AV:231
high_cool_sasp
AV:237
dmdhhon
AV:217
s_hmzlev
AV:414
iaq_channel
AV:7
aq_pos1
AV:196
aq_pos2
AV:197
aq_pos3
AV:198
aq_spd1
AV:199
aq_spd2
AV:200
aq_spd3
AV:201
161
VALUE
CCN POINT
ID
RANGE
EQUIVALENT
0 to 1
DAMPACT
0 to 1
DAMPCMD
0 to 999999
ST_DAMP
0 to 1
S_DAMPER
5 to 300
ECONOTRV
0 to 55
EFFDB
–40 to 245
TEMP_EFF
55 to 90
EFFSP
0 to 20
OAERAEDB
0 to 1
ETSPRH
–40 to 240
ETSPT
–40 to 245
FST
–20 to 0
FBDLO_SP
35 to 80
FBDH_SAT
0 to 240
FBDSATSP
10 to 60
FBDH_SST
0 to 9999
FILTLEFT
0 to 1
FSPD_FCL
0 to 90
MAXFREET
–30 to 70
MINFREET
0 to 65535
RS_FREEC
0 to 999999
HR_FREEC
0 to 999999
ST_FREEC
0 to 65535
RS_FLOAD
–2 to 2
HDMD_LUP
0 to 40
HTDOLEV1
0 to 40
HTDOLEV2
0 to 40
HTDOLEV3
60 to 600
H_MINOFF
60 to 600
H_MINON
0 to 65535
HEATMSTG
40 to 80
HSP_EFF
0 to 55
HEATSH1
0 to 55
HEATSH2
0 to 55
HEATSH3
–99 to 99
HTDTREND
0 to 65535
RS_HTR_1
0 to 999999
HR_HTR_1
0 to 999999
ST_HTR_1
0 to 600
TIMGD_H1
0 to 65535
RS_HTR_2
0 to 999999
HR_HTR_2
0 to 999999
ST_HTR_2
0 to 600
TIMGD_H2
2 to 10
HCSP_GAP
10 to 600
HEAT_FOD
0.2 to 1
FSPD_HT
40 to 125
OATLHEAT
–100 to 100
HEAT_DMD
0.5 to 20
DMDHCON
0.2 to 1
FSPD_HCL
40 to 80
HCSASP
0.5 to 20
DMDHHON
0 to 2
S_HMZLEV
0 to 3
IAQ_CHAN
0 to 1
AQ_POS1
0 to 1
AQ_POS2
0 to 1
AQ_POS3
0 to 1
AQ_SPD1
0 to 1
AQ_SPD2
0 to 1
AQ_SPD3