CONTROL SET POINT AND CONFIGURATION LOG
DISPLAY TEXT
INDOOR FAN (cont)
IDF VFD VOLTAGE
IDF VFD NOM. FREQ
IDF VFD NOM. AMPS
IDF VFD NOM. RPM
IDF VFD MIN REF
IDF VFD MAX REF
VFD ACCEL. TIME
VFD DECEL. TIME
IDF VFD MAX AMPS
IDF VFD TIMEOUT
IDF VFD RESET DUR
VFD RFI FILTER
ECONOMIZER
ECON INSTALLED?
ECON MAX POS
ECON TRAVEL TIME
MINIMUM POSITION
CONFIGS
MIN POS@ MAX FAN
MIN POS SPEED 1
MIN POS DAMP 1
MIN POS SPEED 2
MIN POS DAMP 2
MIN POS SPEED 3
MIN POS DAMP 3
FREE COOL CONFIGS
LOW COOL SAT SP
HIGH COOL SAT SP
FREE COOL MAX OAT
FREE COOL MIN OAT
DIFF DRY BULB CTL
DIFF DB DEADBAND
ENTHALPY HI LIMIT
Table AC — Settings Main Menu Layout (cont)
EXPANDED TEXT
IDF VFD Motor Volts
IDF VFD Motor Freq.
IDF VFD Motor Current
IDF VFD Motor Nom. RPM
IDF Danfoss Min Ref
IDF Danfoss Max Ref
IDF VFD Accel. Time
IDF VFD Decel. Time
IDF VFD Max Current
IDF Danfoss Comm. TO
IDF Danfoss Auto Reset
IDF Danfoss RFI Filter
Economizer Configurations
Menu
Economizer Installed?
Econ Max Damper Position
Economizer Travel Time
Minimum Position
Configurations Menu
Econ Min at Max Fan Speed
Min Pos – User Speed 1
Min Pos – User Pos 1
Min Pos – User Speed 2
Min Pos – User Pos 2
Min Pos – User Speed 3
Min Pos – User Pos 3
Free Cooling Specific
Configurations Menu
Low Free Cool SAT Setpnt
High Free Cool SAT Setpnt
Free Cooling Max OAT
Free Cooling Min Temp
Diff. Dry Bulb Control
Diff. Dry Bulb Deadband
Max Enthalpy OA Limit
RANGE
UNITS
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
50 to 1000
V
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
20 to 400
Hz
60
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
0.1 to 40
A
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
100 to 60000
rpm
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 14-26)
0 to 65
Hz
0
0 to 65
Hz
60
1 to 1800
sec
10
1 to 1800
sec
10
See VFD Motor
Default
Configuration
Tables.
Table 35 (sizes
0 to 655.35
A
04-06)
Table 42 (Vert.
sizes 07-26)
Table 43 (Horz.
Sizes 07-26)
1 to 600
sec
30
0 to 600
sec
30
On/Off
On
No: no FIOP
Yes/No
Yes: FIOP
0 to 100
%
100
5 to 300
sec
150
0 to 100
%
30
0 to 100
%
0
0 to 100
%
0
0 to 100
%
0
0 to 100
%
0
0 to 100
%
0
0 to 100
%
0
40 to 80
°F
65
40 to 80
°F
55
0 to 90
°F
65
-30 to 70
°F
0
Enable/Disable
Disable
0 to 20
°F
3
1.0 to 99.0
Btu/lb
28
181
DEFAULT
POINT
MOTVOLT
MOTFREQ
MOTCUR
MOTNOMS
P
MINREF
MAXREF
RAMPUP_T
RAMPDN_T
VFD1MAXA
CNT_TOUT
ARSTRT_T
RFIFILTR
ECONO
DAMPMAX
ECONOTRV
MINP_MAX
MP_USPD1
MP_UPOS1
MP_USPD2
MP_UPOS2
MP_USPD3
MP_UPOS3
LCSASP
HCSASP
MAXFREET
MINFREET
DIFFBULB
OATRATDB
FREEMAXE
ENTRY