Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 155

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX D — SYSTEMVU™ CONTROLLER CCN TABLES
TABLE NAME
DISPLAY NAME
ZS Force Unoccup Enable
ZS Force Unocc Wt Delay
Zone Sensor Poll Rate
ZSENSCFG
(cont)
ZS TLO Cont Enable
ZS TLO Set During Occ
Zone Sensor UI Mode
Zone Sensor Unit
System Touch Device Inst
System Touch Poll Rate
TOUCHCFG
System Touch AI for SPT
System Touch AI for SPRH
OAT Sensor Trim Offset
RAT Sensor Trim Offset
FST Sensor Trim Offset
SPT Sensor Trim Offset
SPTO Sensor Offset Trim
SPRH Sensor Trim Offset
IAQ Sensor Trim Offset
TRIM
OAQ Sensor Trim Offset
OARH Sensor Trim Offset
RARH Sensor Trim Offset
Cir.A SSP Sensor Trim
Cir.A SDP Sensor Trim
Econ Fdback Trim Offset
OACFM Sensor Trim Offset
Metric Display
Display Language Select
DISPLAY
LCD Contrast Adjustment
User Password Protection
User Password
Table U — SERVICE CONFIGURATION TABLES (cont)
RANGE
No
No
1 to 100
No
No
1=Dual Offsets
0=degrees F
0 to 4194303
10 to 60
0 to 9999
0 to 9999
–10 to 10
–30 to 30
–10 to 10
–30 to 30
–1 to 1
–15 to 15
–200 to 200
–200 to 200
–15 to 15
–15 to 15
–50 to 50
–50 to 50
–15 to 15
–10 to 10
Yes/No
0=English,
1=Spanish,
2=French,
3=Portuguese
1 to 10
Enable/Disable
0 to 9999
UNITS
POINT NAME
ZSFUNEN
ZSFUNWT
sec
ZSPOLLRT
ZSTLOEN
ZSTLSOC
ZSUIM
ZSUNIT
DEVST
sec
POLLST
AISTSPT
AISTSPRH
°F
OAT_TRIM
°F
RAT_TRIM
°F
FST_TRIM
°F
SPT_TRIM
°F
SPTOTRIM
%
SPRHTRIM
ppm
IAQ_TRIM
ppm
OAQ_TRIM
%
OARHTRIM
%
RARHTRIM
psig
SSPATRIM
psig
SDPATRIM
%
EC1DTRIM
cfm
OCFMTRIM
DISPUNIT
LANGUAGE
LCD_CONT
PASS_EBL
PASSWORD
155
DEFAULT
No
No
5
No
No
1=Dual Offsets
0=degrees F
0
0
0
0
0
0
0
0
0
0
0
0
0
No
0=English
5
Enable
1111