FAULT OR ALERT
A166-OAQ OPEN SENSOR
A167-OAQ SHORTED SENSOR
A168-SPACE RELATIVE
HUMIDITY OPEN SENSOR
A169-SPACE RELATIVE
HUMIDITY SHORTED SENSOR
A170-ECON FEEDBACK RANGE
A171-ECON FEEDBACK OPEN
A172-ECON FEEDBACK
SHORTED
A190-TSTAT HEAT/COOL CALLS Run unit in mode activated first
A191-TSTAT IMPROPER COOL
A192-TSTAT IMPROPER HEAT
F200-FIRE SHUTDOWN
F201-CONDENSATE OVERFLOW Cooling Shutdown
A203-DIRTY FILTER
F204-REMOTE SHUTDOWN
A210-GENERAL STATUS
F211-GENERAL STATUS
F310-CIR.A DOWN DUE TO FAIL
F311-CIR.A LOW CHARGE
A312-CIR.A UNEXPECTED OFF
A313-CIR.A HIGH DISCHARGE
A314-CIR.A HPS TRIP
A315-CIR.A LOW DISCHARGE
A316-CIR.A LOW SUCTION
A317-CIR.A PRESSURE RATIO
F318-COMPRESSOR STUCK ON
F319-C.A1 DOWN DUE TO FAIL
A320-C.A1 REVERSE ROTATION
A321-C.A1 FAIL TO PRESSURE
F322-C.A2 DOWN DUE TO FAIL
A323-C.A2 REVERSE ROTATION
A324-C.A2 FAIL TO PRESSURE
A410-IGC IGNITION FAILURE
F411-ROLLOUT WITHOUT HEAT
F412-RUN AWAY HEAT
A510-INDOOR FAN STATUS
F511-IDF OFF WHEN COMMAND
ON
F512-IDF ONWHEN COMMAND
OFF
F600-IDF VFD COMMUNICATION
F601-IDF VFD UNEXPECTED
F602-IDF VFD LOCKOUT
A603-IDF VFD IN HAND
F604-IDF VFD IN HAND
A605-IDF VFD THERMAL
WARNING
Table 16 — SystemVu™ Controller Alarm Codes (cont)
ACTION TAKEN
BY CONTROL
No OAQ Operations
No OAQ Operations
No dehumidifying
No dehumidifying
No economizer diagnostics
No economizer diagnostics
No economizer diagnostics
Run cooling per number of
active inputs
Run heating per number of
active inputs
Unit Shutdown
Alert Generated
Unit Shutdown
Alert Generated
Unit Shutdown
Shutdown Circuit A
Shutdown Circuit A
Strike for active compressors
Unload compression and up
ODF to High cool speed
Add compressor strikes
Add compressor strikes
Add compressor strikes
Add compressor strikes
Unit in Safety Shutdown
Lockout Compressor A1
Add Strike for compressor A1
Add Strike for compressor A1
Lockout Compressor A2
Add Strike for compressor A2
Add Strike for compressor A2
Lockout Heat
Unit in Safety Shutdown
Unit in Safety Shutdown
Alert Generated
Unit Shutdown
Unit Shutdown
Unit Shutdown
Unit Shutdown
Unit Shutdown
Alert Generated
Unit Shutdown
IDF speed reduced
RESET
METHOD
Automatic
Bad sensor, bad wiring, or incorrectly configured sensor.
Automatic
Bad sensor, bad wiring, or incorrectly configured sensor.
Bad sensor, bad wiring, incorrectly configured sensor, loss of
Automatic
communication to SIOB.
Bad sensor, bad wiring, incorrectly configured sensor, loss of
Automatic
communication to SIOB.
Automatic
Wiring problem with actuator or configuration error.
Automatic
Wiring problem with actuator or configuration error.
Automatic
Wiring problem with actuator or configuration error.
Automatic
Bad thermostat or thermostat wiring.
Automatic
Bad thermostat or thermostat wiring.
Automatic
Bad thermostat or thermostat wiring.
Automatic
Smoke detected by smoke detector.
Automatic
Drain pan plugged, sensor error, or configuration error.
Automatic
Dirty filter or expired filter timer.
Automatic
Remote activation of the shutdown switch.
Automatic
General switch activation or wrong configuration.
Automatic
General switch activation or wrong configuration.
Compressors have 3 strikes or has been locked out by another
Manual
alarm.
Manual
Low refrigerant or faulty pressure transducer.
Compressor failure, transducer failure, or nuisance operating
Automatic
conditions.
An overcharged system, high outdoor ambient temperature
Automatic
coupled with dirty outdoor coil, plugged filter drier, or ODF
speeds being set too low.
An overcharged system, high outdoor ambient temperature
Automatic
coupled with dirty outdoor coil, plugged filter drier, or ODF
speeds being set too low.
An undercharged system, low outdoor ambient temperature
Automatic
coupled with dirty outdoor coil, plugged filter drier, or ODF
speeds being set too high
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
Automatic
transducer, excessively cold return air, or stuck open
economizer when the ambient temperature is low.
Low refrigerant charge, plugged filter drier, faulty transducer,
Automatic
the ambient temperature is low and the ODFs are running too
fast.
Manual
Welded contactor or frozen compressor relay on MBB.
Compressor A1 has 3 strikes or has been locked out by
Manual
another alarm.
Automatic
Wiring causing reverse rotation or faulty compressor.
Automatic
Wiring causing reverse rotation or faulty compressor.
Compressor A2 has 3 strikes or has been locked out by
Manual
another alarm.
Automatic
Wiring causing reverse rotation or faulty compressor.
Automatic
Wiring causing reverse rotation or faulty compressor.
Automatic
Faulty wiring of the IGC, no gas flow, or wrong configuration.
Faulty wiring of the IGC, or rollout switch trip without a heat
Automatic
call.
Automatic
Heat stuck on causing high SAT, or low air flow.
Automatic
Belt broke, motor failure, or configuration error.
Manual
Fan stuck on or incorrect configuration.
Tripped circuit breaker, broken belt, bad indoor fan motor, or
Manual
incorrect configuration.
Communication failure, noise on the bus, wiring error, or
Automatic
configuration error.
Automatic
VFD fault, refer to VFD section.
Power Cycle Cycle VFD locked itself out.
Automatic
VFD keypad used to put the VFD in hand or off mode.
Automatic
VFD keypad used to put the VFD in hand or off mode.
Automatic
Motor improper size, motor overload, or configuration errors.
39
PROBABLE CAUSE