Carrier 48LC Series Controls, Start-Up, Operation And Troubleshooting page 102

Single package rooftop units with systemvu controls version 3.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX A — SYSTEMVU™ CONTROLLER DISPLAY
DISPLAY TEXT
NEW HARDWARE (cont)
ENTHALPY SW CHAN
NETWORK SETTINGS
BAS PROTOCOL
NETWORK TIMEOUT
CCN
BUS NUMBER
CCN ELEMENT #
CCN BAUDRATE
BROADCAST ACK?
BROADCAST SCHEDL?
BROADCAST TIME?
BROADCAST OAT?
BROADCAST OARH?
BROADCAST OAQ?
BROADCAST IAQ?
LOCATION
REFERENCE NUMBER
BACNET
MAC ADDRESS
BACNET BAUDRATE
AUTO ID SCHEME
BACNET AUTO ID
BACNET ID
LINKAGE SETTINGS
DEVICE IAQ
OBJECT ID IAQ
COV IAQ
DEVICE OAQ
OBJECT ID OAQ
COV OAQ
DEVICE OARH
OBJECT ID OARH
COV OARH
DEVICE OAT
OBJECT ID OAT
COV OAT
DEVICE RARH
OBJECT ID RARH
COV RARH
DEVICE RAT
OBJECT ID RAT
COV RAT
DEVICE SPT
OBJECT ID SPT
COV SPT
LOCAL_SHEDL_EDIT
SYSTEM TOUCH
DEVICE INSTANCE
POLLING RATE
Table B — Settings Main Menu Layout (cont)
EXPANDED TEXT
Enthalpy Sw Channel
Building Network Configurations
Menu
BAS Protocol Select
Network Input Timeout
CCN Network Configuration Menu
CCN Bus Number
CCN Element Number
CCN Baud Rate
CCN Broadcast Ack'er
Global Schedule Broadcast
CCN Time Broadcast
Broadcast OAT On Network
Broadcast OARH On Network
Broadcast OAQ On Network
Broadcast IAQ On Network
Device Location
Reference number
BACnet network configuration
menu
BACnet Device Macaddress
BACnet BMS baud rate
ALC Auto ID Scheme
BACnet ID Auto ID
BACnet ID Number
LINKAGE SETTINGS MENU
BACnet device for IAQ
Object instance for IAQ
Change of value for IAQ
BACnet device for OAQ
Object instance for OAQ
Change of value for OAQ
BACnet device for OARH
Object instance for OARH
Change of value for OARH
BACnet device for OAT
Object instance for OAT
Change of value for OAT
BACnet device for RARH
Object instance for RARH
Change of value for RARH
BACnet device for RAT
Object instance for RAT
Change of value for RAT
BACnet device for SPT
Object instance for SPT
Change of value for SPT
Allow Local Sched Edit
System Touch Menu
System Touch Device Inst
System Touch Poll Rate
RANGE
UNITS
0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=NONE,
1=CCN,
x
2=BACNET
0 to 600
min
0 to 239
1 to 239
0=9600,
1=19200,
2=38400
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
text string
text string
1 to 127
0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
Yes/No
Yes/No
0 to 4194302
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
0 to 4194303
0 to 9999
0 to 60
Yes/No
enum
0 to 4194303
10 to 60
102
DEFAULT
POINT
0=None
ENTHCHAN
0=NONE
BMS_CFG
30
NETINTO
0
CCNBUS
1
CCNADD
2=38400
BAUDENUM
No
CCNBCACK
No
CCN_GSBC
No
CCNBC
No
OATBC
No
OARHBC
No
OAQBC
No
IAQBC
<blank>
DEV_LOC
<blank>
REF_NUM
01
BAC_MAC
4=76800
BAC_BAUD
Yes
AUID
Yes
BAC_AUID
1610101
BAC_ID
1610100
DEVIAQ
1009
OBJIAQ
0
COVIAQ
1610100
DEVOAQ
285
OBJOAQ
0
COVOAQ
1610100
DEVOARH
1022
OBJOARH
0
COVOARH
1610100
DEVOAT
1003
OBJOAT
0
COVOAT
1610100
DEVRARH
30
OBJRARH
0
COVRARH
1610100
DEVRAT
1010
OBJRAT
0
COVRAT
1610100
DEVSPT
2007
OBJSPT
0
COVSPT
No
LCL_EDIT
160099
DEVST
10
POLLST

Hide quick links: