MENU M – Set Zone Master (continued)
Date – Choose the day and month of the special day.
Setting – Choose which schedule will run during the special day.
When the clock reaches the selected special day (at 12:00 midnight) the
schedule that is selected for this day will run. When the clock reaches the
end of this day (at 12:00 midnight) the special day schedule will end and the
normal weekday schedule will take over. When (------) is shown, no special
day schedule is set.
This screen will only appear on the Master controller (Unit #1).
The Zone Alarms screens allow all units in the zone to report selected
alarms to the master. Based on the alarm selection, the master will act as
described below. There are up to 34 types of alarms that can be chosen.
Standby (Stby): When the selected alarm occurs in the unit, the Zone
Master temporarily activates a standby unit to supplement the unit in
alarm.
Off: As in standby alarms described above; when the selected alarm
occurs in the unit, the Zone Master activates a standby unit to
supplement the unit that had the alarm. In addition; the master will
reconfigure the unit as Off (for both Primary and Secondary schedules)
so that it will no longer be allowed to run. Once a unit is reconfigured to
be Off, the unit must be set back to standby at the master in order to
resume operation.
However, if all standby units have already been requested to turn on,
the master will not reconfigure the last remaining unit as Off and allow it
to continue to run.

 
        
        
     
    
     
      