MENU C – Clock/Scheduler continued
Day: The day of the week that you want to set in the scheduler. The range of
adjustment is Monday to Sunday with a default value of Monday.
Copy to: The weekday that you want the settings of this day to be copied to. The
range of adjustment is Monday to Sunday with a default value of Monday. Select
"Yes", to initiate the copy process.
1: to 4: The selection of times (in 24hr format) that an action will take place. You
can set up to four timed actions. The range of adjustment is 00:00 (midnight) to
23:59.
Setting: This is the action that should occur at the selected time. This action will
remain until the next timed action for this day. If it is the last timed action for this
day, it will remain effective until the next timed action of the following day. The
default value is to take No Action. There are four possible action settings:
No Action (--------): The scheduler will continue running the last action
taken either this day or the previous day.
Normal SP : Use the normal temperature and humidity settings. This action
will also turn the unit on if it was currently off.
Set-Back: Apply the setback offsets to the normal temperature and
humidity settings. This action will also turn the unit on if it was currently off.
Turn Off: The unit will be turned off until the timed action of Normal SP or
Set-Back is executed. When the unit is off due to the scheduler, the main
status screen will indicate the unit status as OFFbySCH. Caution: The Turn
Off action must be followed by the Normal SP or Set-Back action in order
for the unit to turn back on.







