Alarm Screen
Description &
Classification
Hi Humidity
The return air
humidity is
higher than the
high humidity
alarm limit.
*Warning
Low Humidity
The return air
humidity is
lower than the
low humidity
alarm limit
*Warning
Humidifier
Humidifier
failure
malfunction
*Warning
Possible Causes
No electric reheat
Lack of vapor barrier
Unusual high rate of
building heat gain
Humidity is too High
Humidity alarm set
point needs to be
adjusted
Unusual rate of
building humidity gain
Loose Connection
Out of calibration
Faulty Sensor
Humidity is to low
Humidity alarm set
point needs to be
adjusted
Humidifier not working
properly
Out of calibration
Faulty Humidity
sensor
Low water pressure
Overcurrent detected
or no current
Fill system failure
End of cylinder life
104
Corrective Actions
Check reheat elements for
proper operation
Seal room with the proper vapor
barrier
Check room infiltration
Check humidity in the room
Check High humidity alarm set
point (range 35%-90%)
Check water vapor infiltration
Check Connection
Calibrate sensor
Check Humidity sensor and
replace if needed
Check humidity in the room
Check Low humidity alarm set
point (range 10%-65%)
Check Humidifier
Calibrate sensor
Check Sensor replace if needed
Check water pressure
Check current, and add minerals
to the water if necessary
Check for water supply and fill
valve