Optional Equipment & Features
Electronic Expansion Valve:
stepper motor inside the expansion valve. The module controls refrigerant
superheat and optimizes the efficiency of the refrigerant circuit. It features low
superheat, high evaporation pressure (MOP), and low evaporation pressure (LOP)
protection.
Power Meter Module: The module communicates to the dap4 to allow monitoring
of voltage, amperage, wattage, VA and power consumption (kWh). It also records
daily power use trends for the last 30-day span and offers phase loss alarm
protection. The ultra-compact module measures only
uses only 1.4" of DIN rail space.
Zone Master: A feature that offers multiple dap4 controls a teamwork solution. Up
to sixteen dap4 units may be arranged in the Zone Master network. The unit
designated as the master has menus with selectable features of:
• Minimum number of units that must always be on
• Automatic lead/lag and standby unit rotation
• Activate a standby unit due to particular alarm conditions
• Activate standby units to assist with controlling temperature or airflow
• Inhibit control functions to prevent units from conflicting operations
• Primary and secondary schedules for economical control
• Unified zone airflow control
Idap Communication Card:
installed. It allows a standard PC to communicate with the dap4 controller. It has
an intuitive menu system that includes: System Status, Configuration, Data and
Graphs, Events and Emails and a Points Table. It can be setup to send trending
data for the previous 24-hour period allowing for review and analysis. The idap
card can be used on a stand-alone basis, in place of a BMS system. It can also
operate in conjunction with a BMS system, using BACnet, Modbus TCP/IP or
SNMP protocols.
Rack Sensor Module:
to the dap4 to control fan speed. Sensors can be set to work independently or
arranged in groups. The rack temperature calculation can be set to use the highest
of the sensors or an average of the sensors. The DIN rail mountable module is
small measuring only 4.5" square and 1.7" tall.
Power Cap: Allows the dap4 to continue operation during short term power
interruptions. This feature is valuable where power sources are not reliable or
when power may switch to a stand-by generator.
The module communicates to the dap4 to drive a
A network card with web-based application software
Allows up to 32 rack temperature sensors to be connected
5
3.11" tall by 4.25" long and
Need help?
Do you have a question about the dap4 and is the answer not in the manual?